Table 3.26 Modbus/SNMP/BACnet/Telnet Master Options

Option

Description

Master Poll Interval

This is the amount of time between when a response is received from a Slave
and when the RIM-1000 asks for the next register. This interval is adjustable from
250 to 2000ms.

The interval is active only when the Serial Protocol is set to a Modbus Master
option.

The interval effects the overall scan rate. If the RIM-1000 is configured to read 60
Modbus variables and the poll interval is set to 1000ms (1second), each Modbus
variable will be read approximately once per minute.

Default: 250 mS

Master Retry
Attempts

This value determines how many times the RIM-1000 will request the same regis-
ter when there is no response from the Slave before moving on to read the next
register. This value is adjustable from 1 to 99 seconds.

Default: 1 second

Enable Virtual Slot
#1-4

The number of available virtual slots varies from 1 to 4 depending
on the RIM-1000’s physical configuration.

Virtual slots can only be created if the slot is not occupied by a
physical card. These virtual points can be used in conjunction with
Modbus/SNMP registers to allow individual alarming, notification
and relay activation per Modbus register.

BCM Zero Amp
Level Alarm

Determines if the branch circuit current is zero (CB open or tripped). It is active
when Serial Protocol is set to “Modbus Master BCM - 4 Units” or “Modbus
Master BCM - 16 Units.” This applies to all branch circuits in all the BCMs. Each
branch circuit has a “Zero Amp” Enable to enable or disable the zero amp alarm.
This setting is adjustable from 0 to 1 Amp.

BCM Status Display

Displays the how the BCM status is displayed (i.e, left/right or vertical).

Modbus Slave
Register Display Log

Modbus Packet Log

Modbus/Snmp
Master Poll Data Log

SMS/Text Modem
Log

BACnet Packet Log

BACnet Master Data
Log

The RIM-1000 logs a wide variety of information that is available for
trending and troubleshooting. Access the logged information as
necessary.

A more extensive explanation of these logs and the information
found in them can be found in Chapter 4, “Advanced
Communications - Modbus, BACnet, and Telnet” on page 129.

Reset Modbus Port

This link allows users to reset the Modbus port so that the contents
of the polling registers will be cleared.