www.chatsworth.com

Table 3.3 RIM-1000 Main Board Configuration Options

Option

Description

SNMP Trap
Recipients

Use the Configuration>SNMP/Syslog page to set up your SNMP
Communities. Once communities are configured, their IP address
will appear next to the checkboxes in these fields.

Check the boxes of the recipients that should receive messages
when this input goes into alarm.

High1/Low1 SNMP
Traps

Used to disable SNMP notification for the first level analog alarm.
Notification is not sent until alarm reaches the more critical level 2.

SNMP OID

The SNMP OID is provided here for informational purposes only.

Display Value

Used to show either Signed or Unsigned Values for the displayed
value calculated by the RIM-1000.

Example: If a selected value is Unsigned, the RIM-1000 will not display a
negative number on the calculated reading.

Individual Ground
Type (digital input only)

Only applies to Digital Inputs.

Defines the type of digital input as either Individual Ground or Common Ground.

• Individual Ground: Used if the monitored input is a single relay contact and

two contacts- common and NO or NC-are accessible.

• Common Ground: Used if multiple relays are to be monitored that have the

commons bussed or tied together (only one common input connection) and only
the NO or NC contacts are available for each individual relay output. See
the example below or see 2.2., “RIM-1000 Wiring” on page 21, for more
information.

Example: Configure input channels 1-2 for Individual Ground, and configure input
channels 4-6 for Common Ground:

Figure 3.7 NOI/NC Wiring Example