4.8.

Telnet

The RIM-1000 supports a Telnet connection over IP port 23. When properly configured a Telnet user can use the Com1 port of
the RIM-1000 to communicate to external EIA-232 enabled devices.

4.8.1 Hardware Connections

The Com1 port is located on the back of the RIM-1000. The COM1 Transmit and Receive LEDs are also located on the back of the
RIM-1000.

The EIA-232 port allows communications between the RIM-1000 and one other device (point-to-point connection). The EIA-232
port has maximum cable length of 50 feet (15.2m).

Table 4.11 COM1 DB9 Male Pin Out

Figure 4.15 RIM-1000 Connection to an EIA-232 Device

Connect a nine-pin, straight-through serial cable to the RIM-1000 and to the other device.

Once you connect the serial cable, the RIM-1000 automatically switches to EIA-232 mode.

Pin

Description

Pin 1

Data Carrier Detect

Pin 2

Receive Data

Pin 3

Transmit Data

Pin 4

Data Terminal Ready

Pin 5

Signal Ground

Pin 6

No Connection

Pin 7

Request to Send (internally connected to Pin 8)

Pin 8

Clear to Send (internally connected to Pin 7)

Pin 9

No Connection