D.1.

Configuring a RLE Seahawk device Device as an Analog Input for RIM-1000

Users with legacy systems may find this information useful. The RIM-1000 averages/filters the analog inputs.Therefore, the alarm
delay for the RLE Seahawk LD5100 input must be set to a value equal to or greater than the averaging time set in the RIM-1000.
The LD5100 will output 4mA when there is no leak. The LD5100 will output a value between 4mA and 20mA when there is
a water leak. The low range (4mA) will always correspond to zero feet. The high range (20mA) will always correspond to the
LD5100’s set 4-20mA Max Range (1000, 2500, or 5000 feet).

Figure D.9 LD5100 Distance Read Leak Detection System (4-20mA)