Remote Infrastructure Management System - Version 1.0 / July 2014

Chatsworth Products, Inc. (CPI) • 800-834-4969

135

Table 4.3 Modbus Slave Register Display Log Fields

Column

Description

5

Displays the Contents of the Channel Input Alarm Register. The number displayed
will be the sum of all active alarms. For example, if an input is above the
High1and High2 limits, the number displayed will be 5 (1 + 4 = 5).

0 = No Alarm

1 = High 1 Alarm

2 = Low 1 Alarm

4 = High 2 Alarm

8 = Low 2 Alarm

10 = Digital Alarm

6

Displays the RIM-1000 Slave Register Number for the Channel Input Configuration
Status.

7

Displays the contents of the Channel Input Configuration Register.

0 = Not Installed

1 = Not Configured

2 = Analog 4-20mA

3 = Digital NO

4 = Digital NC

5 = Digital Status

6 = Analog 0–5VDC

7 = Analog 0–10 VDC

8

Provides Additional Information for the RIM-1000 Input

(0) = Input is Not Installed (an Expansion Card not installed for this channel).

(a) = This Channel is an Analog Input (Main Board input or Expansion Card “A”).

(d) = This Channel is a Digital Input (Expansion Card “C”).

(R) = This Channel is a Relay Output.