Chatsworth Products Remote Infrastructure Management (RIM-1000) User Manual

Page 172

Advertising
background image

Remote Infrastructure Management System - Version 1.0 / July 2014

172

www.chatsworth.com

Note: Do not overlook installation of the screw. This screw grounds the expansion card and is critical to the RIM-1000 performance.

6. If the expansion card is to be mounted in the lid (Slots 2, 3, and 4), mount the card as follows:

a. Attach the ribbon cable to the expansion card, making sure that the correct connector is attached.

Note: The ends of the ribbon cable are keyed, which means they will only fit onto the two double rows of pins in one direction.
Align the keyed side of the ribbon cable with the notches in the plastic surrounding the rows of pins and push down securely. Always
place and remove the ribbon cable with a straight up and down motion. Pulling the cable to one side or another will damage the pins
in the connector and damage the board.

Figure A.5 Expansion Card with Ribbon Cable Attached

b. Angle the card toward the front of the RIM-1000 as you slide it into place with the bottom of the card facing out and the terminal

blocks positioned in the rear opening. Align the screw holes on the card with the posts.

Figure A.6 Expansion Card Mounting in a Two-Rack Unit