CALIBRATION AND ADJUSTMENTS

To ensure optimum performance, calibration must be

performed on a regularly scheduled basis. Since

each application is different, the length of time

between regularly scheduled recalibrations can vary

from one installation to the next. In general, the more

frequently a system is checked, the greater the

reliability.

IMPORTANT!

4 to 20 ma devices not manufactured by Det-
tronics must be pre-calibrated. to ensure
adequate protection, calibration must be
performed on a regularly scheduled basis.

Note

If the calibration procedure is not completed
within 12 minutes, the detector will revert back to
the previous calibration values. the red LeD will
blink. the calibration will be logged as aborted.

Note

the “Sensor Replacement” calibration procedure
must be used for the initial calibration of a new
sensor. the “Routine Calibration” procedure can
be used for all subsequent calibrations.

Note

Some calibration procedures require the
operator to activate the reed switch located on a
circuit board inside the junction box. See Figure
5-1 for reed switch location. to activate the
switch, hold the calibration magnet against the
side of the junction box near the switch location
approximately one inch above the mounting
surface. (Do not open the junction box.) Hold
the calibration magnet in place for approximately
4 seconds to initiate the calibration procedure.

CALIBRATION ALGORITHM A
FOR MANUAL CALIBRATION OF UNIVERSAL DCU

Normal Calibration
1. Activate the reed switch. (The red LED blinks

while the reed switch is closed.)

2. After the reed switch has been closed for 3

seconds, the calibrate LED blinks, indicating it is

ready for the zero input.

3. Enter the zero input (4 ma).

4. Activate the reed switch. (The red LED blinks

while the switch is closed.)

5. After the reed switch has been closed for 3

seconds, the communication module records the

uncalibrated value in the calibration log and

calibrates the zero value. (The calibrate LED

stays on steady.)

6. Apply the calibration gas.

7. The calibrate LED blinks as the input increases.

8. Activate the reed switch. (The red LED blinks

while the reed switch is closed.)

9. The communication module records the

uncalibrated value in the calibration log and

calibrates the span value after the reed switch is

on for 3 seconds.

10. The calibrate LED stays on steady.

GND

9

10

7

8

5

6

3

4

1

2

13

14

11

12

A1881

MAGNETIC REED SWITCH

*

*

TO ACTIVATE THE MAGNETIC REED SWITCH,

HOLD THE CALIBRATION MAGNET AGAINST THE SIDE OF THE ENCLOSURE

AT THE LOCATION OF THE REED SWITCH,

APPROXIMATELY ONE INCH ABOVE THE MOUNTING SURFACE.

SW1

Figure 5-1—DCU Terminal Wiring Board Mounted in Six-Port

Junction Box