Section 6 - specifications, Eq3xxx controller – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 112

Advertising
background image

14.1

95-8533

6-1

Section 6

Specifications

note

For USCG Approved System specifications, refer
to Appendix D.

EQ3XXX CONTROLLER

INPUT VOLTAGE—

24 vdc nominal, 18 to 30 vdc. 10% overvoltage will

not cause damage to the equipment.

INPUT POwEr—

9 watts nominal, 12 watts maximum.

LON cOmmUNIcATION—

Digital communication, transformer isolated (78.5

kbps).

rS-485 cOmmUNIcATION—

MODBUS Master/Slave capability.

Digital communication, transformer isolated (up to

115 kbps).

rS-232 cOmmUNIcATION—

S3 configuration only.

Digital communication, optically isolated.

cONTrOLNET—

Digital communication, transformer isolated (5 Mbps).

SErIAL INTErfAcE bOArd—

RS-485 Communication

: MODBUS master/slave

capability, ground fault monitored.

Digital communication, transformer isolated (up to

230 kbps).
RS-232 Communication

: MODBUS master/slave or

S3 configuration capability.

Digital communication, non-isolated (up to 230 kbps).
RS-232 Communication

: MODBUS master/slave

capability.

Digital communication, non-isolated (up to 230 kbps).
High Speed Serial Link (HSSL)

: Port used only for

redundant controller to controller communication.

UNSUPErVISEd OUTPUTS—

Dry Contact Rating: 1 ampere at 30 vdc maximum.

SPDT normally open/normally closed contact,

Configurable for normally energized or de-energized

(de-energized is the default mode).

UNSUPErVISEd INPUTS—

Two State input (on/off). User selectable normally

open or normally closed contact (N.O. is the default).

TrOUbLE OUTPUT—

SPDT normally open/normally closed contact,

Non-Configurable, normally energized only.

TEmPErATUrE rANGE—

Operating (ordinary locations, Det-Tronics verified):

–40°F to +185°F (–40°C to +85°C).

Operating (Certified Rating):

See Certification section below.

Storage:

–40°F to +185°F (–40°C to +85°C).

Excluding communication port optional modules.

HUmIdITY rANGE—

5 to 95% RH, non-condensing.

VIbrATION—

FM 3260, FM 6310/6320.

dImENSIONS—

See Figure 6-1.

SHIPPING wEIGHT—

5 pounds (2.3 kilograms).

cErTIfIcATION—

FM / CSA: Class I, Div. 2, Groups A, B, C, D (T4).

Class I, Zone 2, Group IIC (T4).

Tamb = –40°C to +80°C.

Performance verified.

Refer to Appendix A for FM Approval details,

including Protected Premises Fire Alarm Systems and

EQP Supervising Systems.

Refer to Appendix B for CSA Certification details.

Refer to Appendix D for USCG Approval details.

CE:

ATEX/EMC Directive Compliant.

ATEX:

FM

APPROVED

II 3 G.

Ex nC IIC T4 Gc.

EN 60079-29-1 & EN 60079-29-4.

DEMKO 02 ATEX 133867X.

Tamb* = –40°C to +80°C.

Tamb = –40°C to +70°C.

IECEx:

IECEx ULD 10.0004X.

Ex nC IIC T4 Gc.

Tamb* = –40°C to +80°C.

Tamb = –40°C to +70°C.

Note: Refer to Appendix C for ATEX and IECEx

approval details and Special Conditions for Safe Use.
*Applicable only if relays 1-7 (terminals 21-41) are

configured such that the relay contacts are normally

open and de-energized (refer to Figures 3-8 and 3-9

for relay wiring information).

FM

APPROVED

®

FM

APPROVED

®

FM

APPROVED

®

Advertising