Analog input module installation, Mounting, Wiring – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 59

Advertising
background image

14.1

3-40

95-8533

ANALOG INPUT MODULE

INSTALLATION

MOUNTING
The Analog Input Module must be properly installed in

a suitable enclosure that is rated for the location. The

enclosure must provide space to install and wire the

device and must also provide for ground wire

termination. Access into the enclosure must be gained

by using a special tool to open the enclosure. The

enclosure should be rated for the temperature range

of the location plus the temperature rise of all

equipment installed inside the enclosure. The

enclosure must be rated for electrical equipment that

is going to be installed.

NOTE

It is recommended to maintain a minimum of 4
inches clearance between the module and other
equipment to provide adequate room for wiring
and ventilation.

WIRING
All electrical connections are made to the field wiring

connectors furnished with the module. (Connectors

accept up to 12 AWG wire.) Refer to Figure 3-46 for

identification of module wiring terminals.

Power Connector — Terminals 1 to 6
24 vdc Power Input
1 — +

2 — –

3 — Shield*

4 — +

5 — –

6 — Shield*

*Shields on power wires are optional unless required

by local codes.

Connect the module power supply to terminals 1 and

2. If additional terminals are required for powering

other devices, these devices should be connected to

terminals 4 and 5. Shields are to be connected to

terminals 3 and 6.

COM Connector — Terminals 1 to 6
LON Terminals
Be sure to observe polarity when wiring the LON.

1 — "A" side of signaling circuit for COM 1

2 — "B" side of signaling circuit for COM 1

4 — "A" side of signaling circuit for COM 2

5 — "B" side of signaling circuit for COM 2

3 & 6 — shield connections (shields required).

CHANNEL 8

CHANNEL 7

CHANNEL 6

CHANNEL 5

CHANNEL 4

CHANNEL 3

CHANNEL 2

CHANNEL 1

COM

6

5

4

3

2

1

COM 2 SHLD
COM 2 B
COM 2 A
COM 1 SHLD
COM 1 B
COM 1 A

SHLD

B
A

SHLD

B
A

LON FROM

PREVIOUS DEVICE

LON TO

NEXT DEVICE

POWER

6

5

4

3

2

1

SHLD

+
SHLD

+

SHLD

*


+

SHLD

*


+

24 VDC

INPUT VOLTAGE

24 VDC

INPUT VOLTAGE

EQ3710AIM

TO

EARTH

GROUND

A2224

+ SUPPLY A

4-20 MA IN B

COMMON C

+ SUPPLY A

4-20 MA IN B

COMMON C

+ SUPPLY A

4-20 MA IN B

COMMON C

+ SUPPLY A

4-20 MA IN B

COMMON C

+ SUPPLY A

4-20 MA IN B

COMMON C

+ SUPPLY A

4-20 MA IN B

COMMON C

+ SUPPLY A

4-20 MA IN B

COMMON C

+ SUPPLY A

4-20 MA IN B

COMMON C

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

*

SHIELDS ON POWER WIRES ARE OPTIONAL

UNLESS REQUIRED BY LOCAL CODES.

Figure 3-46—Analog Input Module Wiring Terminal Configuration