Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 107

Advertising
background image

14.1

95-8533

5-5

Note

Pressing the Sensor Replacement Switch
prevents the communication module from
generating a fault signal when the input drops to
zero due to sensor removal. the calibration will
not be aborted if the calibration procedure is not
completed within 12 minutes.

3. Replace the sensor.

4. Wait at least 5 minutes for the sensor output to

stabilize.

5. Activate the reed switch. (The red LED flashes for

3 seconds while the switch is activated.) The

communication module records the uncalibrated

value in position one of the calibration log and

calibrates the zero value. (The calibrate LED

stays on steady.)

6. Apply the calibration gas. (The calibrate LED

flashes when the input increases.)

7. Activate the reed switch. (The red LED flashes for

3 seconds while the switch is activated.)

8. The communication module records the

uncalibrated value in the first register of the

calibration log and calibrates the span value. (The

calibrate LED stays on steady.)

9. Remove the calibration gas and replace the DCU

enclosure cover.

10. The communication module waits until the analog

value drops below 4% full scale. The calibration

is complete. (The calibrate LED turns off.)

Note

Pressing the Sensor Replacement Switch aborts
the calibration and starts over.

CALIBRATION ALGORITHM D
FOR UNIVERSAL DCUs wITH O2 SENSOR

Normal Calibration
1. Apply clean air (20.9% oxygen).

2. Activate the reed switch for at least 4 seconds.

(The red LED flashes for 3 seconds while the

switch is closed.)

3. The calibrate LED flashes, indicating calibration

has begun.

4. The communication module waits 3 seconds.

5. The communication module records the

uncalibrated value in the calibration log and

calibrates the span value.

6. The calibrate LED stays on steady.

7. The communication module waits 3 seconds.

8. Calibration is complete. (The calibrate LED turns

off.)

Sensor Replacement

wARNING!

the hazardous area must be de-classified prior
to removing a junction box cover with power
applied.

1. Open the junction box cover and press the

Sensor Replacement Switch.

2. The calibrate LED on the communication module

flashes, indicating it is ready for the zero input.

3. Replace the sensor and set the Sensor Switch

(located on the sensor cell) to zero.

4. Activate the reed switch. (The red LED flashes for

3 seconds while the switch is closed.)

5. The communication module records the

uncalibrated value in position one of the

calibration log and calibrates the zero value. The

calibrate LED stays on steady.

6. Set the Zero Switch on the sensor to the “normal”

position. Apply clean air (20.9% oxygen) to set

the sensor analog span value.

7. The calibrate LED flashes when the input goes

high.

8. Activate the reed switch. (The red LED flashes for

3 seconds while the switch is closed.)

9. The communication module records the

uncalibrated value in the first register of the

calibration log and calibrates the span value.

10. The calibration is complete. The calibrate LED

turns off.

Note

Pressing the sensor replacement switch aborts
the calibration.