14.1

95-8533

4-2

CONTROLLER STATUS INDICATORS
System status is visually displayed on the Controller

in two ways — through the use of a Text Display (see

Figure 4-2), and through colored LED’s (see Table

4-1). The following paragraphs describe these

indicators and the function of each.

TEXT DISPLAY
The Controller uses a text based display to show

current system status, active Alarms and Faults.

When an alarm or trouble condition occurs, the

display scrolls a detailed message of the condition,

including tag number, condition (alarm, trouble,

supervisory etc.) and time/date. If multiple alarms or

trouble conditions exist, the display scrolls through all

active status conditions until they go inactive and are

reset using the controller pushbutton.

CONTROLLER MENU OPTIONS
The Controller is designed to display system status

and device related information. The following

paragraphs describe how to move around within the

controller’s menu structure to access this information

and perform minor system settings (see Figure 4-3).

Note

During normal operation (no alarms or trouble
conditions occurring), the display scrolls current
system time and date.

Main Menu

displays a list of options to access

information types available for display through the

Controller. This list also includes access to options

used to set system date and time, and diagnostics

options.

LED Function

Status

Green Power On when power is applied.
Red

Fire Alarm

On (latched) when any fire alarm is active (Fire detected).

Amber Trouble

On (latched) when a fault is detected in the system. (Indicates "Trouble" relay state.)

Amber Ack

On when the Acknowledge button is pressed.

Amber Silence

On when Silence pushbutton is pressed.

Amber Inhibit

On when any input channel is inhibited.

Amber

Out Inhibit

On when any output is inhibited.

Red

High Gas

On (latched) when any gas detector is at or above the High gas alarm value.

Red

Low Gas

On (latched) when any gas detector is at or above the Low gas alarm value.

Amber Supr

On (latched) when any Supervisory input is active.

Amber

LON Fault

On when a LON fault is detected (open or short).

Amber

Contrl Fault

On when a processor fault occurs.

Fire Alarm

Inhibit

Power

Supr

High Gas

Trouble

Cntrl Flt

Lon Fault

Low Gas

Ack

Silence

Out Inhibit

Eagle Quantum Premier

Time & Date

EAGLE QUANTUM PREMIER
Safety System Controller

Fire Alarm

Inhibit

Power

Supr

High Gas

Trouble

Cntrl Flt

Lon Fault

Low Gas

Ack

Silence

Out Inhibit

Eagle Quantum Premier

Time & Date

Cancel

Enter

Next

Previous

Reset

Acknowledge Silence

DET

-

TRONICS

®

Table 4-1—EQP Controller LED System Status Indicators