3-49

14.1

95-8533

EQ22XXDCU DIGITAL COMMUNICATION UNIT
USED WITH POINTWATCH/DUCTWATCH
Determine the best mounting location for the detector.

Whenever practical, detectors should be placed

where they are easily accessible for calibration.

WARNING!

Do not apply power to the system with the cover
removed unless the area has been verified to be
free of combustible gases and vapors.

The DCU utilizes the following:

1. A terminal wiring board mounted at the bottom of

the junction box.

2. A communication module mounted above the

terminal wiring board using the standoffs

provided. See Figure 3-60.

Assembly and Wiring Procedure
Attach the PointWatch/DuctWatch to the DCU

enclosure. Do not over-tighten. If a sensor

separation kit is being used, attach the sensor to the

separation kit junction box and wire the device as

described in the “Sensor Separation” section.

Refer to the PointWatch instruction manual (form

number 95-8440) or the DuctWatch instruction manual

(form number 95-8573) for complete installation and

application information.

Refer to Figure 3-63 when wiring a PointWatch IR gas

detector and a DCU. The wiring code for PointWatch

is:

Red =

+ (24 vdc)

Black =

– (common)

White =

4 to 20 ma signal

Yellow =

Calibration input

Green =

Chassis ground

Set the address for the device. Refer to “Setting

Device Network Addresses” for complete information

regarding the switch setting procedure.

Sensor Separation for DCU with PointWatch
Shielded four wire cable is recommended for

connecting the detector junction box to the DCU.

Cable with a foil shield is recommended. The shield

of the cable should be open at the detector junction

box and connected to earth ground at the DCU

junction box.

NOTE

To ensure proper operation, it is essential to
maintain a minimum of 18 vdc (including ripple)
at the PointWatch detector.

1

2

3

4

5

6

7

8

9

10

YELLOW

WHITE

BLACK

RED

GREEN

DCU

POINTWATCH

14

13

12

11

+

+

24 VDC

POINTWATCH CALIBRATE

4 TO 20 MA IN

+

A

B

A

B

SENSOR POWER

COM 2

COM SHIELD

COM 1

A1876

Figure 3-63—PointWatch/DuctWatch Connected to DCU