Configuration, 8 channel relay module installation, Mounting – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 57: Wiring

Advertising
background image

14.1

3-38

95-8533

NOTE

In EQP systems with EQP2120PS(–B) Power
Supplies, the secondary power is customer
supplied and must be accepted by the Authority
Having Jurisdiction (AHJ).

Unsupervised Output Ancillary Applications
(Unrelated to Fire Detection/Protection)
Connect external wiring to the appropriate terminals

on the DCIO terminal block. See Figure 3-44.

NOTE

No connection should be made to the “+ Supply”
terminal.

CONFIGURATION

Setting DCIO Network Address
One unique network address must be assigned to

each DCIO module. The address is set by the 8

switch DIP assembly on the DCIO module. The

address is binary coded and is the sum of all

switches placed in the “closed” position.

Each discrete point of a DCIO module has a tag

number and a descriptor for unique identification. A

tag number must include zone designation, which will

be shown on the controller's display when the point is

in alarm.

Det-Tronics S

3

Safety System Software is used for

device configuration. The following shows the

minimum software/firmware releases:

8 CHANNEL RELAY MODULE

INSTALLATION

The following paragraphs describe how to properly

install and configure the 8 Channel Relay Module.

MOUNTING
The Relay Module must be properly installed in a

suitable enclosure that is rated for the location. The

enclosure must provide space to install and wire the

relay module and must also provide for ground wire

termination. Access into the enclosure is gained by

using a special tool to open the enclosure. The

enclosure should be rated for the temperature range

of the location plus the temperature rise of all

equipment installed inside the enclosure. The

enclosure must be rated for electrical equipment that

is going to be installed. The device can be panel or

DIN rail mounted.

NOTE

It is recommended to maintain a minimum of 4
inches clearance between the module and other
equipment to provide adequate room for wiring
and ventilation.

WIRING
All electrical connections are made to the field wiring

connectors furnished with the module. See Figure

3-45 for terminal identification.

Table 3-13—Maximum Wire Length for FM Approved Solenoids for Deluge and Pre-Action Applications

Solenoids

Maximum Wire Length in Feet (Meters)

FM Solenoid Group Manufacturer

Model

12 AWG

14 AWG

16 AWG 18 AWG

B

ASCO

T8210A107

183 (56)

115 (35)

72 (22)

46 (14)

D

ASCO

8210G207

314 (96)

198 (60)

124 (38)

78 (24)

E

Skinner

73218BN4UNLVNOC111C2

331 (101)

208 (63)

131 (40)

82 (25)

F

Skinner

73212BN4TNLVNOC322C2

130 (40)

82 (25)

51 (16)

32 (10)

G

Skinner

71395SN2ENJ1NOH111C2

331 (101)

208 (63)

131 (40)

82 (25)

H

Viking

HV-274-0601

180 (55)

110 (34)

70 (21)

45(14

)

Figure 3-44—Unsupervised Output Configuration

+ SUPPLY A

IN– / OUT+ B

COMMON C

1

2

3

NOTE: SHUNT/FLYBACK DIODES DO NOT NEED

TO BE INSTALLED ON THE FIELD DEVICE.

CIRCUIT PROTECTION IS PROVIDED

WITHIN THE DCIO.

A2323

Controller Firmware

S3

Revision

Version

Version

A

1.03

2.0.2.0