Eq3740ipm intelligent protection module – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 119

Advertising
background image

14.1

95-8533

6-8

EQ3740IPM INTELLIGENT

PROTECTION MODULE

POwEr rEQUIrEmENTS—

3 watts nominal, 7 watts maximum.

INPUT VOLTAGE—

24 vdc nominal, 18 to 30 vdc. 10% overvoltage will

not cause damage to the equipment.

LON cOmmUNIcATIONS—

Digital communication, transformer isolated (78.5

kbps).

TEmPErATUrE rANGE—

Operating: –40°F to +185°F (–40°C to +85°C).

Storage:

–67°F to +185°F (–55°C to +85°C).

HUmIdITY rANGE—

0 to 95% RH, non-condensing.

dImENSIONS—

Refer to Figure 6-3.

SHIPPING wEIGHT—

1 pound (0.45 kilograms).

CERTIFICATION

FM / CSA:

Class I, Div. 2, Groups A, B, C, D (T4).

Class I, Zone 2, Group IIC (T4).

Special conditions for safe use:

Electronic assembly must be installed in a suitable

NRTL labled NEMA rated enclosure.

INPUT / INITIATING DEVICE CIRCUITS - CONTACT
MONITOR TYPE - CHANNEL 1 - 3

note

An input must be active for at least 750
milliseconds in order to be recognized.

UNSUPErVISEd INPUT—

Two state input (on/off).

Normally open contact.

No EOL resistor required.

SUPErVISEd INPUT, cLASS b—

Two state input (active/trouble):

End of Line Resistor 10 K ohms ±20%

Open Circuit > 45 K ohms

Active Circuit < 5 K ohms.

SUPErVISEd INPUT, cLASS b—

Three State input (active/short/open):

End of Line Resistor 10 K ohms ±20%

In Line Resistor 3.3 K ohms ±20%

Open Circuit > 45 K ohms

Short Circuit < 1.4 K ohms

Active Circuit 2.5 K ohms to 5 K ohms.

INPUT CIRCUITS - TWO WIRE SMOKE/HEAT TYPE -
CHANNEL 4 AND 5

SUPErVISEd INPUT, cLASS b:

Up to 15 two wire detectors per circuit.

Maximum line resistance 50 ohms

5K ohm EOL

Open circuit fault impedance 22K ohms

OUTPUT / NOTIFICATION / RELEASING OR
UNSUPERVISED DEVICE CIRCUITS - CHANNEL 6-8

UNSUPErVISEd OUTPUT rATING—

Rating: 2 amperes at 30 Vdc maximum.

Note: Voltage available at outputs is dependent on

input voltage (Vout ≈ Vin – 0.5 Vdc).

OUTPUT STYLE—

Form "A" normally off.

rESPONSE TImE—

Output actuates in <0.15 second after acknowledging

an alarm command message.

No EOL resistor required.

Advertising