Local operating network (lon) – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 12

Advertising
background image

14.1

95-8533

2-6

During normal operation one controller acts as the

“Master” while the other acts as the “Hot Standby”.

Terminology used for redundancy:

master controller

This is the normal mode for

non-redundant and master

controllers. User logic is

executed, outputs are being

controlled and all serial ports

are active.

standby controller

This controller is receiving all

inputs but does not have any

control over the outputs and

user logic is not executed. The

standby controller receives

update information from the

master controller to ensure a

bumpless transfer should a

controller switchover occur.

primary controller

T h e co n t rol l e r a s s ig n e d

address 1.

secondary controller

T h e co n t rol l e r a s s ig n e d

address 2.

Bumpless transfer

During a controller switchover

no change in output will occur

due to the switchover.

serial interface Board
An optional serial board is available that supports up

to four additional serial ports. See Table 2-4. For a

redundant controller configuration, the board is

required in both controllers.

Controller-to-Controller Communication (sLC485)
The EQP controllers can be configured to

communicate with up to 12 controllers via RS-485

communication. The controller-to-controller scheme

provides the ability to meet NFPA 72 SLC requirements

with the following primary features:

• Modular trouble and alarm configuration
• Multiple zone application with controller-to-controller

communication

• Multiple media options.

EQp supervising system (EQpss)
The Det-Tronics EQP controllers can be supervised

via the EQPSS using PCs and HMI. Each EQPSS PC

can communicate with up to 12 EQP controllers over

an Ethernet. This is a Det-Tronics solution. Please

consult the factory for more information.

EQp marine application system
For information regarding EQP Marine Application

Systems, refer to Appendix D.

LoCaL opERatinG nEtWoRK (Lon)
The LON is a fault tolerant, two wire, digital

communication network. The circuit is arranged in a

loop starting and ending at the Controller. The circuit

supports up to 246 intelligent field devices spread

over a distance of up to 10,000 meters (32,500 feet).

note

All Lon devices support AnSI/nFPA 72 Class X
communication with the Controller.

network Extenders
Transmitted signals can travel a maximum distance of

2,000 meters through LON communication wire. At

the end of this distance, a network extender (see

Figure 2-7) must be installed to rebroadcast the

communications into the next wire segment. For

every network extender added, the length of the

communications loop extends up to 2,000 meters.

Due to propagation delays around the loop, the

maximum loop length is limited to 10,000 meters.

noteS

A n e t wo r k ex te n d e r i s re q u i re d fo r
communication loops greater than 60 nodes.

port name

Comm Function

Serial Port 2

RS485 ModBus (Master/Slave)

Ground Fault Monitored,

Isolated

Serial Port 3

RS232 ModBus (Master/Slave)

S3 Configuration

Serial Port 4

RS232 ModBus (Master/Slave)

HSSL Redundancy RS232 Redundant Controller to
Port

Controller Only

Table 2-4—Ports on Optional Serial Interface Board

Advertising