Configuration – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 64

Advertising
background image

3-45

14.1

95-8533

Supervised Output
Notification Supervised for Open & Short Circuits
Connect external system wiring to the appropriate

terminals on the terminal block. See Figure 3-58.
The output of the IPM supervises the notification circuit

by reversing the polarity of the monitoring circuit.

Polarity must be observed when connecting the

notification device. It is essential to utilize a notification

device approved for fire alarm notification. These

devices are polarized and would not require the use of

an external diode for the supervision of the circuit. Wire

one or more notification devices to the output, with a 10

K ohm, 1/4 watt EOL resistor in parallel across the last

device.
No connection should be made to “+ Supply” terminal.

Each output channel is individually activated for

response pattern:

– supervisory

– continuous output

– 60 beats per minute

– 120 beats per minute

– temporal

– trouble.

Channels 7 and 8, Terminals 19 to 24
Supervised Output Agent Release
Connect external system wiring to the appropriate

terminals on the terminal block. See Figure 3-59.
No connection should be made to “+ Supply” terminal.
The output of the IPM supervises the releasing circuit via

the coil of the releasing solenoid. It is essential to utilize

a releasing device approved for use with this output

module. This type of output does not require the use of

EOL resistors or diodes to supervise the circuit.
The output can be configured for continuous or timed

response.
To ensure adequate operating voltage for the output

device, the maximum wiring length from the power

source to the output device must not exceed the values

shown in Table 3-15 for automatic release applications

or Table 3-16 for deluge and pre-action applications.
For solenoids, this wire length includes both the wiring

from the power supply to the IPM and the wiring from the

module to the solenoid.

NOTE

For FM system approval listing, pre-action and
deluge applications require that only FM approved
deluge valves can be wired into the IPM module.
Remember that the valves must utilize 24 vdc and
must not exceed 2 amperes current draw.

CONFIGURATION

Setting Module Network Address
One unique network address must be assigned to

each intelligent protection module. The address is set

by the 8 switch DIP assembly on the module. The

address is binary coded and is the sum of all

switches placed in the “closed” position.

Each discrete point of an intelligent protection module

has a tag number and a descriptor for identification.

Det-Tronics S

3

Safety System Software is used for

device configuration. The following shows the

minimum software/firmware releases:

+ SUPPLY A

IN– / OUT+ B

COMMON C

16

17

18

EOL

RESISTOR

10 K

B2094

Figure 3-58—CH-6: Supervised Output Configuration (Notification)

+ SUPPLY A

IN– / OUT+ B

COMMON C

19

20

21

NOTE: SHUNT/FLYBACK DIODES DO NOT NEED

TO BE INSTALLED ON THE FIELD DEVICE.

CIRCUIT PROTECTION IS PROVIDED

WITHIN THE IPM.

Figure 3-59—CH-7&8: Supervised Output Configuration (Agent Release)

Controller Firmware

S3

Revision

Version

Version

B

3.06

2.9.0.1

Table 3-15—Maximum Wire Length for Releasing Applications

*Fenwal Solenoid
**Ansul Solenoid

Device

Maximum Wire Length in Feet

12 AWG 14 AWG 16 AWG 18 AWG

890181*

150

100

60

895630*

150

100

60

897494*

190

120

75

570537**

3000

1900

1200

750