14.1

95-8533

6-10

EQP2XX0PS(–X) POWER SUPPLIES

INPUT VOLTAGE—

EQP2110PS(-P), EQP2120PS(-B): Auto selectable for

120/220 Vac, –15%, +10%; 60/50 Hz, single phase;
EQP2410PS(-P) Converter: 24 Vdc, –15%, +10%.

INPUT cUrrENT—
EQP2110PS(-P):

3.2 A max @ 120 Vac

1.7 A max @ 220 Vac

EQP2120PS(-B):

6.6 A max @ 120 Vac

3.6 A max @ 220 Vac

EQP2410PS(-P):

15.7 A @ max @ 24 Vdc

OUTPUT VOLTAGE—

24.5 Vdc nominal, 24.5 to 28.0 Vdc.

OUTPUT cUrrENT—
EQP2110PS(-P):

10 A

EQP2120PS(-B):

20 A

EQP2410PS(-P):

10 A

TEmPErATUrE rANGE (all models)—

Operating:

–13°F to +131°F (–25°C to +55°C)

(All Applications)
Storage:

–40°F to +185°F (–40°C to +85°C)

HUmIdITY rANGE—

5 to 95% RH at 25°C, non-condensing.

dImENSIONS—

In Inches (Centimeters)

Width Height Depth

EQP2110PS(-P):

3.35(8.5) 5.2(13.0) 5.0(12.5)

EQP2120PS(-B):

3.54(9) 5.2(13.0) 5.0(12.5)

EQP2410PS(-P):

3.2(8.0) 5.2(13.0) 5.0(12.5)

note

Power supplies are designed for DIn rail or
panel mounting (–B or –P suffix).

cErTIfIcATION—

FM / CSA: Ordinary locations.

USCG:

Refer to Appendix D for details.

REDUNDANCY MODULE QUINT–DIODE/40

TEmPErATUrE rANGE—

Operating:

–13°F to +131°F (–25°C to +55°C)

(All Applications)
Storage:

–40°F to +185°F (–40°C to +85°C).

HUmIdITY rANGE—

5 to 95% RH, non-condensing.

dImENSIONS—

in Inches (Centimeters)

Width

Height

Depth

2.4 (6.2)

4 (10.2)

3.3 (8.4)

Advertising