Controller to controller communication, Tronics – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 38

Advertising
background image

3-19

14.1

95-8533

Use Port 2 to pass safety critical information between

controllers. User logic can pass all alarm, trouble,

and supervisory information between the controllers.

Watchdog timers must be implemented in user logic

to verify the integrity of the SLC. Consult the local

authority having jurisdiction for annunciation

requirements.

CONTROLLER TO CONTROLLER COMMUNICATION

Controller to Controller Communication (SLC485)
with Signaling Line Circuit Classification
Class B or X, per NFPA 72
To connect up to twelve controllers together and be

able to transfer safety information between the

controllers, the communication link must be classified

as a signaling line circuit per NFPA 72. With the serial

board option, Port 2 (plug 10) is a RS-485 serial

connection that is ground fault monitored.

To meet the signaling line circuit (Class B or Class X)

requirements, the following must be configured for

correct operation:
• All controllers must have the optional serial board.
• The Termination jumper P28 must be set to

Terminate (position 1-2) on all controllers.

• The Ground Fault Monitor jumper P29 must be set to

Enabled (position 1-2) on all controllers.

• For Class X, Connect terminals A (# 56) and B (# 55)

between the controllers. Connect terminal A (# 60) and

B (# 61) between controllers using a different cable route.

Connect GND (# 54) to GND (# 62) on each controller.

• For Class B, connect terminals A (terminal number

60) and B (terminal number 61) between the

controllers. The GND (terminal number 62) must not

be connected.

See Figure 3-13 for wiring details.

Note 1: 56.7 kbps minimum and 115.2 kbps maximum

baud rate required for proper communication.

Note 2: Consult the factory for configuration set-up.

Note 3: Maximum SLC485 length over copper not to

exceed 1000 meters.

Controller to Controller with Fiber Optic Link, Signal
Line Circuit Classification Class B or X per NFPA 72.
Up to twelve EQP controllers (single or redundant

pair) can be inter-connected via a fiber optic link. This

communication link is classified as a signaling line

circuit per NFPA 72 to allow safety information to be

transferred between controllers.

60

62

61

61

63

65

64

67

64

67

66

68

P28: RS-485 Termination Jumper,

Position 1 & 2

P29: RS-485 Ground Fault

Monitor Jumper, Position 1 & 2

A

B

P28

1

3

P29

1

3

P12

PORT 4

P11

PORT 3

P10

PORT 2

60

62

63

65

66

68

P28: RS-485 Termination Jumper,

Position 1 & 2

P29: RS-

485 Ground Fault

Monitor Jumper, Position 1 & 2

A

B

P28

1

3

P29

1

3

P12

PORT 4

P11

PORT 3

P10

PORT 2

GND

A

B

GND

A

B

D2276

TO

ADDITIONAL

CONTROLLER(S)

54

55

56

54

55

56

EAGLE QUANTUM PREMIER
Safety System Controller

Fire Alarm

Inhibit

Power

Supr

High Gas

Trouble

Cntrl Flt

Lon Fault

Low Gas

Ack

Silence

Out Inhibit

Eagle Quantum Premier

Time & Date

Cancel

Enter

Next

Previous

Reset

Acknowledge Silence

DET

-

TRONICS

®

EAGLE QUANTUM PREMIER
Safety System Controller

Fire Alarm

Inhibit

Power

Supr

High Gas

Trouble

Cntrl Flt

Lon Fault

Low Gas

Ack

Silence

Out Inhibit

Eagle Quantum Premier

Time & Date

Cancel

Enter

Next

Previous

Reset

Acknowledge Silence

DET

-

TRONICS

®

Figure 3-13—Controller to Controller Communication with Class A Signaling Line Circuit Classification per NFPA 72