Eq3700 direct current io (dcio) module, Eq3700 discrete io (dcio) module – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 116

Advertising
background image

14.1

95-8533

6-5

EQ3700 DISCRETE IO (DCIO)

MODULE

POwEr rEQUIrEmENTS—

3 watts nominal, 11 watts maximum.

INPUT VOLTAGE—

24 vdc nominal, 18 to 30 vdc. 10% overvoltage will

not cause damage to the equipment.

21 to 30 vdc for Pre-action / Deluge application.

NOTE: For deluge and pre-action applications, input

voltage to the device must be 21 vdc minimum to ensure

proper operation of the connected output device.

OUTPUT VOLTAGE—

(Input voltage – 0.5 vdc) @ 2 amperes.

OUTPUT cUrrENT—

10.0 amperes maximum total current, 2.0 amperes

maximum per channel.

LON cOmmUNIcATION—

Digital communication, transformer isolated (78.5

kbps).

TEmPErATUrE rANGE—

Operating: –40°F to +185°F (–40°C to +85°C).

Storage:

–67°F to +185°F (–55°C to +85°C).

HUmIdITY rANGE—

5 to 95% RH, non-condensing.

dImENSIONS—

Refer to Figure 6-3.

SHIPPING wEIGHT—

1 pound (0.45 kilograms).

cErTIfIcATION—

FM / CSA: Class I, Div. 2, Groups A, B, C, D (T4).

Class I, Zone 2, Group IIC (T4).

Refer to Appendix A for FM Approval details.

Refer to Appendix B for CSA Approval details.

CE:

ATEX/EMC Directive Compliant.

ATEX:

FM

APPROVED

II 3 G.

Ex nA nC IIC T4 Gc.

DEMKO 02 ATEX 133864X.

Tamb = –40°C to +85°C.

IECEx:

IECEx ULD 10.0004X.

Ex nA nC IIC T4 Gc.

Tamb = –40°C to +85°C.

Note: Refer to Appendix C for ATEX and IECEx

approval details and Special Conditions for

Safe Use.

INPUT / INITIATING DEVICE CIRCUITS
UNSUPErVISEd INPUT—

Two state input (on/off).

Normally open contact.

SUPErVISEd INPUT, cLASS b—

Two state input (active/trouble):

– End of Line Resistor 10 K ohms nominal

– Open Circuit > 45 K ohms

– Active Circuit < 5 K ohms.

SUPErVISEd INPUT, cLASS b—

Three State input (active/short/open):

– End of Line Resistor 10 K ohms nominal

– In Line Resistor 3.3 K ohms nominal

– Open Circuit > 45 K ohms

– Short Circuit < 1.4 K ohms

– Active Circuit 2.5 K ohms to 5 K ohms.

INPUT, TYPES—

Configurable for fixed logic applications:

– Fire Alarm

– Supervisory

– Trouble

– High Gas Alarm

– Low Gas Alarm

– Other.

FM

APPROVED

®

FM

APPROVED

®

FM

APPROVED

®

Advertising