Controlnet status indicators (optional) – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 84

Advertising
background image

14.1

95-8533

4-7

Note

If multiple alarms are present, “Acknowledging”
will silence the audible alarms.

CONTROLNET STATUS INDICATORS
(Optional)
The optional ControlNet status indicator LEDs function

as follows: (see Table 4-3)
Steady - The indicator is on continuously in the

defined state.
Alternating - The two indicators alternate between the

two defined states at the same time (applies to both

indicators viewed together). The two indicators are

always in opposite states, out of phase.
Flashing - The indicator alternates between the two

defined states (applies to each indicator viewed

independent of the other). If both indicators are

flashing, they must flash together, in phase.

SEQUENCE OF EVENTS DURING A
CONFIGURATION DATA DOWNLOAD
During a configuration download, the controller

receives configuration data that is stored into flash

memory. During the download process, the controller

halts normal operation and resets a number of

controller functions. Items affected and displayed

during a configuration data download are listed in the

following steps:

1. Halt the static logic and user logic programs.

2. Ignore field device LON communications.

However, the controller continues to generate the

LON heartbeat.

3. Silence the Controller’s audible annunciator.

4. Initiate a Trouble condition that is signaled by the

amber Trouble LED and relay.

5. Clear all Alarm and Fault events.

6. De-energize all 8 Controller relays.

7. Ignore Modbus communication.

0.5 SEC

0.5 SEC

1.5 SEC

FIRE

ALARM

0.5 SEC

0.5 SEC

3.0 SEC

HIGH/LOW

GAS

0.5 SEC

5.0 SEC

TROUBLE

0.1 SEC

0.1 SEC

2.0 SEC

SUPERVISORY

B1855

Figure 4-4—Tone Pattern for Controller Buzzer