14.1

95-8533

6-11

EQ21XXPSM POWER SUPPLY MONITOR

INPUT VOLTAGE—

24 vdc nominal, 18 to 30 Vdc.

POwEr cONSUmPTION—

2.0 watts maximum.

mEASUrEmENT rANGE—

AC Voltage:

240 vac maximum.

DC Battery Charging Current: 75 amperes maximum.

OUTPUT—

Digital communication, transformer isolated (78.5 k bps).

TEmPErATUrE rANGE—

Operating: +32°F to +122°F (0°C to +50°C)

Storage:

–67°F to +185°F (–55°C to +85°C).

HUmIdITY rANGE—

5 to 95% RH, non-condensing.

dImENSIONS—

See Figure 6-4.

cErTIfIcATION—

FM / CSA: Ordinary locations.

EQ22xxIDC/IDCGF INITIATING

DEVICE CIRCUIT

INPUT VOLTAGE—

24 vdc nominal, 18 to 30 vdc. 10% overvoltage will

not cause damage to the equipment.

INPUT POwEr—

4.0 watts maximum.

INPUTS—

Two supervised non-incendive digital inputs (sealed

or unsealed switch or relay contacts). 10 kohm EOL

resistors are required.

OUTPUTS—

Digital communication, transformer isolated (78.5

kbps).

TEmPErATUrE rANGE—

Operating: –40°F to +167°F (–40°C to +75°C).

Storage:

–67°F to +185°F (–55°C to +85°C).

HUmIdITY rANGE—

5 to 95% RH, non-condensing.

VIbrATION—

FM 3260.

dImENSIONS—

See Figure 6-5.

B

C

J1

J3

4

(10.2)

8.5

(21.6)

9

(22.9)

2.5

(6.4)

2.25

(5.7)

A2038

figure 6-4—dimensions of Power Supply monitor in Inches (cm)

3.46

(8.8)

4.7

(11.9)

2.7

(6.9)

5.2

(13.2)

5.86

(14.9)

6.57

(16.7)

1.28

(3.3)

A2523

figure 6-5—dimensions of Tall cover Junction box in Inches

(centimeters)

Advertising