Eq2220gfm ground fault monitor – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 123

Advertising
background image

14.1

95-8533

6-12

cErTIfIcATION—

FM / CSA:

Class I, Div. 1, Groups B, C, D.

Class I, Zone 1, Group IIC.

Class II/III, Div. 1, Groups E, F, G.

Class I, Div. 2, Groups A, B, C, D (T4).

Class I, Zone 2, Group IIC (T4 ).

Class II/III, Div. 2, Groups F & G (T4).

NEMA/Type 4X.

Refer to Appendix A for FM Approval details.

Refer to Appendix B for CSA Approval details.

CE:

ATEX/EMC Directive Compliant.

Refer to Appendix C for ATEX Approval details.

ATEX:

0539

FM

APPROVED

II 2 G

Ex d IIC T4-T6 Gb

DEMKO 02 ATEX 131321X

T6 (Tamb = –55°C to +50°C)

T5 (Tamb = –55°C to +65°C)

T4 (Tamb = –55°C to +75°C)

IP66

IEC:

IECEx ULD 10.0010

Ex d IIC T4-T6 Gb

T6 (Tamb = –55°C to +50°C)

T5 (Tamb = –55°C to +65°C)

T4 (Tamb = –55°C to +75°C)

Refer to Appendix E for CE Mark details.

EQ2220GFM GROUND FAULT MONITOR

INPUT VOLTAGE—

24 vdc nominal, 18 to 30 vdc. 10% overvoltage will

not cause damage to the equipment.

INPUT POwEr—

1.0 watt maximum.

OUTPUT—

Form C NO/NC relay contact rated 1 ampere

(resistive) at 30 Vdc maximum.

TEmPErATUrE rANGE—

Operating: –40°F to +185°F (–40°C to +85°C).

Storage:

–-67°F to +185°F (–55°C to +85°C).

HUmIdITY rANGE—

5 to 95% RH, non-condensing.

dImENSIONS—

See Figure 6-6.

SHIPPING wEIGHT—

0.5 pounds (0.2 kilograms)

cErTIfIcATION—
FM / CSA:

Class I, Div. 2, Groups A, B, C, D (T4).

Class I, Zone 2, Group IIC (T4 ).

Refer to Appendix A for FM Approval details.

Refer to Appendix B for CSA Approval details.

CE:

ATEX/EMC Directive Compliant.

ATEX:

FM

APPROVED

II 3 G

Ex nC IIC T4 Gc

DEMKO 03 ATEX 136222X

Tamb = –40°C to +85°C

IECEx:

IECEx ULD 10.0004X

Ex nC IIC T4 Gc

Tamb = –40°C to +85°C

Note: Refer to Appendix C for ATEX Approval and

Appendix E for CE Mark details and Special

Conditions for Safe Use.

Refer to Appendix D for USCG Approval details.

1.2

(3.0)

2.9

(7.4)

1.75

(4.4)

2.1

(5.3)

A2237

figure 6-6—dimensions of Ground fault monitor

in Inches (centimeters)

FM