Eq21xxpsm power supply monitor, Eq2220gfm ground fault monitor – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 95

Advertising
background image

14.1

95-8533

4-18

EQ21xxPSM POWER SUPPLY MONITOR

The power supply monitor (see Figure 4-10) has three

LEDs used to provide a visual indication of device

status:

EQ2220GFM GROUND FAULT MONITOR

The ground fault monitor (see Figure 4-11) has three

LEDs used to provide a visual indication of device

status:

Note

the Ground Fault Monitor LeD will respond
immediately to a ground fault condition. the
relay contact requires the condition to exist for 10
seconds before it activates.

LED

Device Status

+ GND FLT LED

Indicates Amber in the presence of a “+”
ground fault.

– GND FLT LED

Indicates Amber in the presence of a “–”
ground fault.

POWER LED

Indicates Green when the unit is
powered.

Table 4-15—Ground Fault Monitor Status Indicators

+ GND FLT LED

– GND FLT LED

PWR LED

A2243

Figure 4-11—Ground Fault Monitor Status Indicator Location

LED

Device Status

Green

When On indicates power is supplied to device.

Red

When Flashing indicates an alarm or fault
condition is present.

Amber

When on indicates device is disabled. Module
must be replaced.

Table 4-14—Power Supply Monitor Status Indicators

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+