Appendix e - ce mark, Appendix e – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 151

Advertising
background image

95-8533

14.1

B-1

95-8533

E-1

APPENDIX E

CE MArk

EMC DirECtivE 2004/108/EC DEtails
The Eagle Quantum Premier Fire and Gas Detection/Releasing System was tested and found to be compliant with

EN61000-6-2, EN61000-6-4, EN50130-4, and EN50270. The following considerations must be given for installation

of the Eagle Quantum Premier system.

• For shielded cable installed in conduit, attach the wire shields to the “shield” connections on the terminal blocks, or

to the earth ground on the case.

• For installations without conduit, use double shielded cable. Terminate the outer shield to the earth ground on the

case. Terminate the inner shield to the “shield” connection on the terminal blocks.

aDDitional DirECtivEs

• ATEX Directive: 94/9/EC

Refer to Appendix C for details.

• Low Voltage Directive: 2006/95/EC

• WEEE Directive: 2002/96/EC

Advertising