System configuration, Setting device network devices, Typical applications – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 76

Advertising
background image

3-57

14.1

95-8533

SYSTEM CONFIGURATION

SETTING DEvICE NETWORK ADDRESSES

Overview of Network Addresses
Each device on the LON must be assigned a unique

address. Addresses 1 to 4 are reserved for the

controller. Valid addresses for field devices are from

5 to 250.

IMPORTANT

If the address is set to zero or an address above
250, the communication module will ignore the
switch setting.

Duplicated addresses are not automatically detected.

Modules given the same address will use the number

given and report to the controller using that address.

A "Rogue Device" message will be displayed when

two LON devices have duplicate addresses assigned

to them. The status word will show the latest update,

which could be from any of the reporting modules

using that address.

Setting Field Device Addresses
Selection of the node address for field devices is

done by setting rocker switches on an 8 switch “DIP

Switch” within each device’s housing.

NOTE

Only the first eight of the 12 switches are used
for selecting the device address.

The address number is binary encoded with each

switch having a specific binary value with switch 1

being the LSB (Least Significant Bit). (See Figure

3-71) The device’s LON address is equal to the

added value of all closed rocker switches. All “Open”

switches are ignored.

NOTE

The address switches in the DCIO module and
relay module appear slightly different than those
in other devices. Refer to Figure 3-72.

Example

: for node No. 5, close rocker switches 1

and 3 (binary values 1 + 4); for node No. 25, close

rocker switches 1, 4 and 5 (binary values 1 + 8 + 16).

NOTE

The field device sets the LON address only when
power is applied to the device. Therefore, it is
important to set the switches

before applying

power. If an address is ever changed, system
power must be cycled before the new address
will take effect.

After setting address switches, record the address

number and device type on the “Address Identification

Chart” provided with this manual. Post the chart in a

convenient location near the Controller for future

reference.

TYPICAL APPLICATIONS

Figure 3-73 is a simplified drawing of a typical EQP

system. This system includes an EQP Controller,

DCIO and various LON field devices.

1 2 3 4 5 6 7 8

1 2 4 8 16 32 64 128

ON

NODE ADDRESS EQUALS THE ADDED VALUE

OF ALL CLOSED ROCKER SWITCHES

A2190

BINARY

VALUE

CLOSED = ON

OPEN = OFF

Figure 3-72—Address Switch for DCIO and Relay Module

1 2 3 4 5 6 7 8

1 2 3 4

1 2 4 8 16 32 64 128

OPEN

OPEN

LEAVE IN

OPEN POSITION

NODE ADDRESS EQUALS THE ADDED VALUE

OF ALL CLOSED ROCKER SWITCHES

A1557

BINARY

VALUE

CLOSED = ON

OPEN = OFF

Figure 3-71—Field Device Address Switches for

ARM, SAM, DCU and IDC

Advertising