General start-up procedures – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 99

Advertising
background image

14.1

95-8533

4-22

Ground Fault Monitor

Verify earth ground connections as specified in the

wiring instructions.

Check power distribution to ensure that all devices

are receiving power.

DCUs

Verify correct address setting.
Check modules for correct orientation.
Check for the presence of contaminants or poisoning

agents.

Device should be oriented with the sensor pointing

down.

IDCs

Verify correct address setting.
Check for correct installation of EOL resistors.

ARMs

Verify correct address setting.
Check jumpers.

SAMs

Verify correct address setting.
Check signal circuits for correct polarity.
Check for correct installation of EOL resistors.
Check jumpers.

GENERAL START-UP PROCEDURES
1. Output loads that are controlled by the system

should be secured (remove power from all output

devices) to prevent actuation.

2. Check all system wiring for proper connection.

3. Inspect all devices to verify that they have not

been physically damaged in shipment.

4. Apply power to the system.

Note

to prevent the network modules from going into
a fault isolation condition, apply power to the
eQP Controller prior to applying power to the
network devices.

5. Program the system for the desired operation

using Det-Tronics Safety System Software (S3).

Download configuration data to all devices.

Note

After system configuration has been completed,
the entire system should be tested for proper
operation to ensure that configuration was
performed properly.

6. Calibrate the sensors.

7. Ensure that all trouble and alarm conditions have

been cleared and the EQP Controller is reset, then

remove mechanical blocking devices (if used)

and restore power to the output loads.