Configuration – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 60

Advertising
background image

3-41

14.1

95-8533

Channel Connectors — Terminals 1 to 24
4-20 mA Input Devices
Connect external wiring to the appropriate terminals

on the analog input module terminal block. See

Figure 3-47 for an example of a 2-wire input. See

Figure 3-48 for a 2-wire input with HART interface

module. See Figure 3-49 for a 3-wire input, where the

transmitter must source a 4-20 mA signal. See Figure

3-50 for a 3-wire input with HART interface module.

Only channel 1 is shown in each diagram. The

information is typical for channels 2-8.

Analog Input Module Channels used as NFPA 72
Approved 4-20 mA Flame Detector Input
Configure the High Alarm setpoint at 19 mA via the S

3

configuration screen, and use the High Alarm to

trigger the Fire Alarm in S

3

logic. The AIM sends an

exception message for the High Alarm so there is no

delay in transmitting the Fire Alarm.

Fault indications and other status information must be

decoded in logic from the analog process variable. A

five second delay should be used to avoid indicating

an incorrect status condition while the analog value is

changing between two values. See Table 3-14.

CONFIGURATION

Setting Analog Input Module Network Address
One unique network address must be assigned to

each analog input module. The address is set by the

8 switch DIP assembly on the analog input module.

When using the switches located on the analog input

module, the address is binary coded and is the sum

of all switches placed in the “closed” position.

Each point of an analog input module has a tag

number and a descriptor for unique identification. A

tag number must include zone designation, which will

be shown on the controller's display when the point is

in alarm.

Det-Tronics S

3

Safety System Software is used for

device configuration. The following tables show the

minimum software/firmware releases:

+ SUPPLY A

4-20 MA IN B

COMMON C

CHANNEL 1

1

2

3

A2235

+

SIG

TRANSMITTER

+ SUPPLY A

4-20 MA IN B

COMMON C

CHANNEL 1

1

2

3

A2236

+

SIG

TRANSMITTER

+ SUPPLY A

4-20 MA IN B

COMMON C

CHANNEL 1

1

2

3

+ SUPPLY

4-20 MA IN

COMMON

HIM

1

4

2

5

3

6

A2238

+

SIG

TRANSMITTER

+ SUPPLY A

4-20 MA IN B

COMMON C

CHANNEL 1

1

2

3

A2239

+

SIG

TRANSMITTER

+ SUPPLY

4-20 MA IN

COMMON

HIM

1

4

2

5

3

6

Figure 3-47—Two-Wire Transmitter — Non-Isolated 4 to 20 mA

Current Output (Sourcing)

Figure 3-49—Three-Wire Transmitter — Non-Isolated 4 to 20 mA

Current Output (Sourcing)

Figure 3-48—Two-Wire Transmitter with HART Interface Module —

Non-Isolated 4 to 20 mA Current Output (Sourcing)

Figure 3-50—Three-Wire Transmitter with HART Interface Module —

Non-Isolated 4 to 20 mA Current Output (Sourcing)

Controller Firmware*

AIM

S3

Rev.

Version

Rev. Version

Version

B

3.06

B

1.02

2.9.1.1

*for part number 007606-002

For Gas Applications

Controller Firmware*

AIM

S3

Rev.

Version

Rev. Version

Version

C

5.52

D

1.07

4.0.0.0

*for part number 008983-001

For Flame Applications

Table 3-14—Analog Values (in mA) for Fault and Status Indications

when the AIM is Used as a 4-20 mA Flame Detector Input

Status

X3301/2

X5200

X9800

X2200

Fault

0-3.5

0-3.5

0-3.5

0-3.5

IR Pre-Alarm

7.0-9.0

UV Alarm

11.0-12.99

IR Alarm

13.0-14.99

Pre-Alarm

15.0-16.99 15.0-16.99 15.0-16.99