Eq3710aim analog input module, Hart interface module (him) – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 118

Advertising
background image

14.1

95-8533

6-7

EQ3710AIM ANALOG INPUT MODULE

POwEr rEQUIrEmENTS—

Module power consumption: 6 watts.

When supplying power to three-wire transmitters:

Maximum current at power input: 7.4 amperes.

Output current: 900 mA per channel maximum.

INPUT/OUTPUT VOLTAGE—

24 vdc nominal, 18 to 30 vdc. 10% overvoltage will

not cause damage to the equipment.

TEmPErATUrE rANGE—

Operating: –40°F to +185°F (–40°C to +85°C).

Storage: –67°F to +185°F (–55°C to +85°C).

HUmIdITY rANGE—

0 to 95% RH, non-condensing.

cHANNEL AccUrAcY—

Zero: ±0.3% full scale from –40°C to +85°C.

Span: ±0.5% full scale from –40°C to +85°C.

rESPONSE TImE—

1 to 100 LON devices:

< 2 seconds

101 to 200 LON devices: < 3 seconds

201 to 246 LON devices: < 4 seconds.

LON cOmmUNIcATION—

Digital communication, transformer isolated (78.5 kbps).

dImENSIONS—

Refer to Figure 6-3.

SHIPPING wEIGHT—

1 pound (0.45 kilograms).

cErTIfIcATION—

FM / CSA:

Class I, Div. 2, Groups A, B, C, D (T4).

Class I, Zone 2, Group IIC (T4).

Refer to Appendix A for FM Approval details.

Refer to Appendix B for CSA Approval details.

CE:

ATEX/EMC Directive Compliant.

ATEX:

FM

APPROVED

II 3 G.

Ex nA nC IIC T4 Gc EN60079-29-1.

DEMKO 03 ATEX 136207X.

Tamb = –40°C to +85°C.

IECEx:

IECEx ULD 10.0004X.

Ex nA nC IIC T4 Gc.

Tamb = –40°C to +85°C.

Note: Refer to Appendix C for ATEX and IECEx

approval details and Special Conditions for

Safe Use.

Refer to Appendix D for USCG Approval details.

HART INTERFACE MODULE (HIM)

INPUT VOLTAGE—

24 vdc nominal, 18 to 30 vdc. 10% overvoltage will

not cause damage to the equipment.

INPUT POwEr—

1.0 watt maximum.

INPUT/OUTPUT cUrrENT—

Operating: 4 -20 mA.

Maximum: 0-30 mA.

TEmPErATUrE rANGE—

Operating: –40°F to +185°F (–40°C to +85°C).

Storage:

–-67°F to +185°F (–55°C to +85°C).

HUmIdITY rANGE—

5 to 95% RH, non-condensing.

dImENSIONS—

See Figure 6-2.

SHIPPING wEIGHT—

0.5 pounds (0.2 kilograms)

cErTIfIcATION—

FM / CSA:

Class I, Div. 2, Groups A, B, C, D (T4).

Class I, Zone 2, Group IIC (T4 ).

CE:

ATEX/EMC Directive Compliant.

ATEX

FM

APPROVED

II 3 G.

Ex nA IIC T4 Gc.

DEMKO 04 ATEX 136507X.

Tamb = –40°C to +85°C.

IECEx:

IECEx ULD 10.0004X.

Ex nA IIC T4 Gc.

Tamb = –40°C to +85°C.

Note: Refer to Appendix C for ATEX and IECEx

approval details and Special Conditions for

Safe Use.

FM

APPROVED

®

FM

APPROVED

®

FM

APPROVED

®

FM

APPROVED

®

Advertising