3-55

14.1

95-8533

Supervised Output for Deluge and Pre-action
Connect external wiring to the appropriate terminals

on the terminal block. See Figure 3-67. Wire one or

more releasing devices to the module output.

The output of the Agent Release Module supervises

the releasing circuit via the coil of the releasing

solenoid. It is essential to use a releasing device

approved for use with this output module.

NOTE

This type of output does not require the use of
EOL resistors or diodes to supervise the circuit.

The output can be configured for latching, continuous

or timed response.

To ensure proper operating voltage, the input voltage

to the release module must be in the range from 21 to

30 vdc and the maximum wiring length must not

exceed the values shown in Table 3-20 for deluge and

pre-action applications. Per FM Approval

requirements, the secondary power must provide

capacity for a 90 hour minimum standby operation

followed by a minimum of 10 minutes of releasing and

alarm operation. The initiating device circuit(s) for

use with the deluge and pre-action system
configuration must be wired within 20 feet and in
conduit from an IDC or DCIO.

In addition, power for

the device(s) must be per NFPA 72 Class A wiring

techniques.

NOTE

In EQP systems with EQP2120PS(–B) Power
Supplies, the secondary power is customer
supplied and must be accepted by the Authority
Having Jurisdiction (AHJ).

Jumpers
Terminals 13 and 14 are connected by jumper JP2

and terminals 11 and 12 are connected by jumper

JP3. These two jumpers (JP2 and JP3) must be cut if

an auxiliary output power supply is being used. (See

Figure 3-68 for jumper locations.)

When an explosive initiator is being used, jumper JP1

must be cut. If a solenoid is used, the jumper must

remain in.
Address Setting
Set the device network address. (See “Setting Device

Network Addresses” in this section.)

EQ25XXSAM SERIES SIGNAL AUDIBLE MODULE

Mounting
The device should be securely mounted to a vibration

free surface. (See “Specifications” in this manual for

device dimensions.)

Wiring

IMPORTANT!

To ensure adequate operating voltage for the
signaling device, the maximum wiring length
from the power source to the output device must
not exceed the values shown in Table 3-21. (This
wire length includes both the wiring from the
power supply to the signal audible module and
the wiring from the module to the signaling
device.)

See Figure 3-69 for identification of wiring terminals.

9 10

7 8

5 6

3 4

1 2

1314

1112

JP1

JP2
JP3

A1902

Figure 3-68—Agent Release Module Wiring Terminals and Jumpers

Maximum Wire Length in Feet (Meters)

12 AWG

14 AWG

16 AWG

(4 mm2)* (2.5 mm2)* (1.5 mm2)*

One 2 Ampere Load

190 (58)

120 (37)

75 (23)

Two 2 Ampere Loads

95 (29)

60 (18)

35 (11)

T0029A

* Approximate Metric Equivalent.

Table 3-21—Maximum Wiring Length

from Nominal 24 VDC Power Source to Signaling Device