14.1

95-8533

WIRING

Power Wiring

CAUTION!

Input voltage at the Controller must be 18 vdc
minimum to ensure proper operation.

It is important to consider both the wire gauge and the

distance from the Controller to the power supply. As

the distance between the Controller and the power

supply increases, so must the diameter of the power

wiring in order to maintain a minimum of 18 vdc at the

Controller.

IMPORTANT!

To ensure proper operation of devices, the
voltage input to the device (measured at the
device) must be within the range indicated for
that device in the "Specifications" section of this
manual.

Electrical Connections
Figure 3-8 shows the location of wiring connectors on

the Controller module. Figure 3-9 identifies individual

terminals.

Connector P1, Terminals 1 to 4 —
24 vdc Input Power
Connect the power supply to terminals 1 and 2 of the

Controller. Terminals 3 and 4 must also be connected

to power.

When controller and power supplies are installed in

separate NRTL cabinets, two power cables from two

distribution circuits are required, so that if one is lost,

the controller will continue to operate and signal a

trouble condition. The power circuit must be

protected against physical damage.

Shields on power cables must be connected to

chassis ground (earth).

P9: TERMINALS 57 TO 59

RS-232 S3 CONFIGURATION PORT

P11: TERMINALS 63 TO 65 – PORT 3

RS-232 MODBUS RTU MASTER/SLAVE

OR S3 CONFIGURATION

P12: TERMINALS 66 TO 68 – PORT 4

RS-232 MODBUS RTU MASTER/SLAVE

P10: TERMINALS 60 TO 62 - PORT 2

RS-485 MODBUS RTU MASTER/SLAVE

P8: TERMINALS 54 TO 56 - PORT 1

RS-485 MODBUS RTU MASTER/SLAVE

P7: TERMINALS 48 TO 53

LON CONNECTIONS

P6: TERMINALS 45 TO 47

FAULT RELAY (NC CONTACT)

P5: TERMINALS 33 TO 44

RELAYS 5 TO 8

P4: TERMINALS 21 TO 32

RELAYS 1 TO 4

P3: TERMINALS 13 TO 20

DIGITAL INPUTS 5 TO 8

P2: TERMINALS 5 TO 12

DIGITAL INPUTS 1 TO 4

P1: TERMINALS 1 TO 4

24 VDC INPUT POWER

E2105

EAGLE QUANTUM PREMIER
Safety System Controller

Fire Alarm

Inhibit

Power

Supr

High Gas

Trouble

Cntrl Flt

Lon Fault

Low Gas

Ack

Silence

Out Inhibit

Eagle Quantum Premier

Time & Date

Cancel

Enter

Next

Previous

Reset

Acknowledge Silence

1

4

60

62

63

65

66

68

5

12 13

20 21

32 33

44 45

47

48

53

54

56

57

59

CONTROLNET

BNC CONNECTOR A

CONTROLNET

BNC CONNECTOR B

P13: HIGH SPEED SERIAL LINK (HSSL)

RS-232 (REDUNDANCY ONLY)

DET

-

TRONICS

®

SERIAL COMMUNICATION BOARD

(OPTIONAL)

Figure 3-8—Location of Wiring Terminals on EQP Controller

Advertising