Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 32

Advertising
background image

3-13

14.1

95-8533

WARNING!

If the installation uses catalytic type combustible
gas sensors, it is imperative that lubricants
containing silicone not be used, since they will
cause irreversible damage to the sensor.

5. Install the communication module in the device

enclosure.

NOTE

Be sure the ribbon cable is properly connected.

6. Set the node address for the device. (See “Setting

Device Network Addresses” in this section)

When configuring the EQ22xxIDCGF, its “device

type” should be configured as an initiating device

circuit (IDC).

Both inputs must be configured for a trouble

condition.

Circuit 1 – “Open” indicates a –24 VDC ground

fault condition. “Active” indicates a +24

VDC ground fault condition.

Circuit 2 – “Active” indicates a loss of AC input

power.

“Open” indicates a loss of battery

power.

7. Place the cover on the enclosure and tighten until

snug. DO NOT over tighten.

EQ22xxIDCSC SERIES INITIATING DEvICE
CIRCUIT SHORT CIRCUIT
(Not FM Approved)

The following paragraphs describe how to properly

install and configure the EQ22xxIDCSC Initiating

Device Circuit Short Circuit.

Mounting
The device should be securely mounted to a vibration

free surface. (See “Specifications” in this manual for

device dimensions.

Wiring

CAUTION!

The enclosure should be electrically connected
to earth ground.

1. Remove the cover from the device enclosure.

2. Remove the communication module from the

junction box. Connect external wiring to the

appropriate terminals on device terminal block.

(See Figure 3-4 for terminal block location and

Figure 3-7 for terminal identification.) The input to

the IDCSC consists of a normally open switch with

a 3.3k ohm series resistor, and a 10K ohm, 1/4

watt EOL resistor in parallel across the switch.

NOTE

An EOL resistor must be installed on both IDCSC
inputs (including unused inputs). Wiring
impedance must not exceed 500 ohms. A 3.3K
ohm resistor must be installed in series with the
switch. For correct operation, only one switch
per input can be connected.

3. Check wiring to ensure that ALL connections have

been properly made.

4. Install the communication module in the device

enclosure.

5. Inspect the enclosure O-ring to be sure that it is in

good condition. Lubricate the O-ring and the

threads of the enclosure cover to ease both

installation and future removal of the cover.

NOTE

The recommended lubricant is a silicone free
grease available from Detector Electronics.

NOTE

Be sure the ribbon cable is properly connected.

6. Set the node address for the device. (See “Setting

Device Network Addresses” in this section.)

7. Place the cover on the enclosure and tighten until

snug. Do not over tighten.

Advertising