High speed serial link (hssl), Lon wiring, Wiring – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 41: Mounting, Enclosure requirements, Eq3xxx redundant controller installation

Advertising
background image

14.1

3-22

95-8533

Connector P12, Terminals 66, 67 & 68, Port 4–
RS-232 Modbus RTU Master/Slave (Non-Isolated)
Configuration data downloaded into the controller

configures the serial interface transmission baud rate,

parity check and MODBUS device address for the

serial port. Software selectable baud rates are

9600,19200, 38400, 57600, 115200, and 230400.

Software selectable parity is None, Odd, and Even.

The controller uses 8 data bits with 1 stop bit.

Port Pinout (3-position terminal block)

66 — TXD

67 — RXD

68 — GND

Connector P13 —
RS-232 High Speed Serial Port
This port is dedicated to inter-controller connection

required for redundancy, and is not available for any

other use. This port is automatically configured.

CONFIGURATION

Software Defined Addresses
Det-Tronics Safety System Software (S3) is

programmed with the addresses that are assigned to

the controller when the configuration file is

downloaded into the controller. Addresses define and

configure the Controller’s LON address, Modbus slave

address, and the ControlNet option board address.

Each device on the LON must be assigned a unique

tag number. This tag number must include zone

designation, which will be shown on the Controller's

display when the device is in alarm.

EQ3XXX REDUNDANT CONTROLLER

INSTALLATION

The redundant controllers must be purchased with the

following options for correct installation:
• Serial board
• High-speed serial cable
• LON termination modules (2).

ENCLOSURE REQUIREMENTS
The redundant controllers must be located next to

each other in the same enclosure (4 ft. interconnecting

cable).

MOUNTING
The controllers are designed for direct panel mounting

or DIN rail mounting. See “Specifications” section of

this manual for mounting dimensions.

WIRING
The redundant controllers are wired the same as a

simplex controller except for the LON wiring and the

dedicated high-speed serial link, which are defined

below. Refer to EQ3XXX Controller Installation for

general installation details.

LON WIRING
The LON must be connected to both redundant

controllers to ensure correct operation. Two LON

Termination Modules are required for the installation

as shown in Figure 3-17.

HIGH SPEED SERIAL LINK (HSSL)
The redundant controllers are connected together by

a dedicated high-speed serial link. This link is a pre-

fabricated cable that has a custom connector for ease

of use. Redundant controllers are automatically

addressed with the HSSL cable. One end of the

cable is labeled Primary. The primary controller takes

address 1, while the secondary controller is address

2. The significance this has for the user is that the

primary is the default master when both controllers

are powered-up at the same time.

C2274

A

B

S

COM 2

A

B

S

COM 1

EQP

CONTROLLER

53

52

51

50

49

48

A

B

S

COM 2

A

B

S

COM 1

EQP

CONTROLLER

53

52

51

50

49

48

NOTE: LON TERMINATION JUMPERS P25 AND P26 (SEE FIGURE 3-12)

MUST BE IN POSITION 2 AND 3 FOR REDUNDANT CONFIGURATION

(ON BOTH CONTROLLERS).

LON

TERMINATION

MODULE

A

3

2

1

6

5

4

B

S

COM 2 TO

FIELD

DEVICES

LON

TERMINATION

MODULE

A

3

2

1

6

5

4

B

S

COM 1 TO

FIELD

DEVICES

Figure 3-17— LON Connection for Redundant EQP Controllers