Eq25xxarm agent release module – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 124

Advertising
background image

14.1

95-8533

6-13

EQ22XXDCU AND EQ22XXDCUEX

DIGITAL COMMUNICATION UNIT

INPUT VOLTAGE—

24 vdc nominal, 18 to 30 vdc. 10% overvoltage will

not cause damage to the equipment.

POwEr cONSUmPTION—

DCU with toxic gas sensor/transmitter: 95 ma max.

DCU with transmitter and combustible gas sensor:

180 ma maximum during normal operation, 500 ma

during startup.

INPUTS—

4 - 20 mA analog signal, non-intrusive calibration.

OUTPUTS—

Digital communication, transformer isolated (78.5 kbps).

TEmPErATUrE rANGE—

Operating: –40°F to +167°F (–40°C to +75°C).

Storage:

–67°F to +185°F (–55°C to +85°C).

HUmIdITY rANGE—

5 to 95% RH, non-condensing.

VIbrATION—

FM 6310/6320.

dImENSIONS—

See Figure 6-5.

cErTIfIcATION—

FM / CSA:

Class I, Div. 1, Groups B, C, D.

Class I, Zone 1, Group IIC.

Class I, Div. 2, Groups A, B, C, D (T4).

Class I, Zone 2, Group IIC (T4 ).

Class II/III, Div. 1 & 2 (for use with Model STB).

NEMA/Type 4X (for use with Model STB).

Refer to Appendix A for FM Approval details.

Refer to Appendix B for CSA Approval details.
CE:

ATEX/EMC Directive Compliant.

ATEX:

0539

FM

APPROVED

II 2 G

Ex d IIC T4-T6 Gb EN 60079-29-1

DEMKO 02 ATEX 131321X

T6 (Tamb = –55°C to +50°C)

T5 (Tamb = –55°C to +65°C)

T4 (Tamb = –55°C to +75°C)

IP66

Refer to Appendix C for ATEX Approval details.
Special conditions for Safe Use (X):

The device has an ambient temperature rating for

performance of –40°C to +75°C.
IEC:

IECEx ULD 10.0010

Ex d IIC T4-T6 Gb

T6 (Tamb = –55°C to +50°C)

T5 (Tamb = –55°C to +65°C)

T4 (Tamb = –55°C to +75°C)

Refer to Appendix D for USCG Approval details.

Refer to Appendix E for CE Mark details.

EQ25xxARM AGENT RELEASE MODULE

rELEASE OUTPUT rATING—

2 amperes at 30 vdc maximum.

SUPErVISOrY cUrrENT—

2.0 ma, ±1.0 ma each circuit.

INPUT VOLTAGE—

24 vdc nominal, 18 to 30 vdc. 10% overvoltage will

not cause damage to the equipment.

NOTE: For deluge and pre-action applications, input

voltage to the device must be 21 vdc minimum to ensure

proper operation of the connected output device.

INPUT cUrrENT—

Standby:

75 ma maximum at 24 vdc.

Alarm:

120 ma maximum at 24 vdc.

STATUS OUTPUTS—

Digital communication, transformer isolated (78.5 kbps).

TEmPErATUrE rANGE—

Operating: –40°F to +167°F (–40°C to +75°C).

Storage:

–67°F to +185°F (–55°C to +85°C).

HUmIdITY rANGE—

5 to 95% RH, non-condensing.

VIbrATION—

Meets MIL SPEC 810C, method 514.2, curve AW.

dImENSIONS—

See Figure 6-5.

cErTIfIcATION—

FM / CSA:

Class I, Div. 1, Groups B, C, D.

Class I, Zone 1, Group IIC.

Class II/III, Div. 1, Groups E, F, G.

Class I, Div. 2, Groups A, B, C, D (T4).

Class I, Zone 2, Group IIC (T4 ).

Class II/III, Div. 2, Groups F & G (T4).

NEMA/Type 4X.

Refer to Appendix A for FM Approval details.

Refer to Appendix B for CSA Approval details.
CE:

ATEX/EMC Directive Compliant.

ATEX:

0539

FM

APPROVED

II 2 G

Ex d IIC T4-T6 Gb

DEMKO 02 ATEX 131321X

T6 (Tamb = –55°C to +50°C)

T5 (Tamb = –55°C to +65°C)

T4 (Tamb = –55°C to +75°C)

IP66

Refer to Appendix C for ATEX Approval details.
IEC:

IECEx ULD 10.0010

Ex d IIC T4-T6 Gb

T6 (Tamb = –55°C to +50°C)

T5 (Tamb = –55°C to +65°C)

T4 (Tamb = –55°C to +75°C)

Refer to Appendix E for CE Mark details.

FM

APPROVED

®

FM

APPROVED

®

FM

APPROVED

®

FM

APPROVED

®

FM

APPROVED

®

FM

APPROVED

®