Intelligent protection module installation, Wiring – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 61

Advertising
background image

14.1

3-42

95-8533

INTELLIGENT PROTECTION

MODULE INSTALLATION

WIRING
All electrical connections are made to the field wiring

connectors furnished with the module. Refer to Figure

3-51 for identification of module wiring terminals.
Power Connector, Terminals 1 to 6
24 vdc Power Input

Connect the module power supply to terminals 1 and

2. If additional terminals are required for powering

other devices, these devices should be connected to

terminals 4 and 5. Shields are to be connected to

terminals 3 and 6 — chassis (earth) ground terminals.

Terminals are rated for 10 amperes. Use both sets of

input terminals in parallel if total output current can

exceed 10 amperes.

LON Connector, Terminals 1 to 6
LON/SLC Signaling Circuit Terminals

Be sure to observe polarity when wiring the LON/SLC.
shield connection — terminals 3 and 6.
1 — "A" side of signaling circuit for COM 1
2 — "B" side of signaling circuit for COM 1
4 — "A" side of signaling circuit for COM 2
5 — "B" side of signaling circuit for COM 2

CHANNEL 8

RELEASE-2

CHANNEL 7

RELEASE-1

CHANNEL 6

BELL

CHANNEL 5

ZONE-2

CHANNEL 4

ZONE-1

CHANNEL 3

SUPERVISORY

CHANNEL 2

MANUAL RELEASE

CHANNEL 1

ABORT

COM

6

5

4

3

2

1

COM 2 SHLD
COM 2 B
COM 2 A
COM 1 SHLD
COM 1 B
COM 1 A

SHLD

B
A

SHLD

B
A

LON FROM

PREVIOUS DEVICE

LON TO

NEXT DEVICE

POWER

6

5

4

3

2

1

SHLD

+
SHLD

+

SHLD

*


+

SHLD

*


+

24 VDC

INPUT VOLTAGE

24 VDC

INPUT VOLTAGE

EQ3740IPM

TO

EARTH

GROUND

A2240

+ SUPPLY A

IN–/OUT+ B

COMMON C

+ SUPPLY A

IN–/OUT+ B

COMMON C

+ SUPPLY A

IN–/OUT+ B

COMMON C

+ SUPPLY A

IN–/OUT+ B

COMMON C

+ SUPPLY A

IN–/OUT+ B

COMMON C

+ SUPPLY A

IN–/OUT+ B

COMMON C

+ SUPPLY A

IN–/OUT+ B

COMMON C

+ SUPPLY A

IN–/OUT+ B

COMMON C

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

*

SHIELDS ON POWER WIRES ARE OPTIONAL

UNLESS REQUIRED BY LOCAL CODES.

Figure 3-51—IPM Wiring Terminal Configuration

Advertising