3-39

14.1

95-8533

Power Connector, Terminals 1 to 6
24 vdc Power Input
1 — +

2 — –

3 — Shield*

4 — +

5 — –

6 — Shield*
*Shields on power wires are optional unless required

by local codes.

Connect the module power supply to terminals 1 and

2. If additional terminals are required for powering

other devices, these devices should be connected to

terminals 4 and 5. Shields are to be connected to

terminals 3 and 6.

COM Connector, Terminals 1 to 6
LON Terminals
Be sure to observe polarity when wiring the LON.

1 — "A" side of signaling circuit for COM 1

2 — "B" side of signaling circuit for COM 1

4 — "A" side of signaling circuit for COM 2

5 — "B" side of signaling circuit for COM 2

3 & 6 — shield connections.

Channel Connectors, Terminals 1 to 24

Unsupervised Output Ancillary Applications
(Unrelated to Fire Detection/Protection)
Connect external wiring to the appropriate terminals

on the relay module terminal block. See Figure 3-45.

CONFIGURATION

Setting Relay Module Network Address
One unique network address must be assigned to

each relay module. The address is set by the 8

switch DIP assembly on the relay module. The

address is binary coded and is the sum of all

switches placed in the “closed” position.

Each discrete point of a relay module has a tag

number and a descriptor for unique identification.

Det-Tronics S

3

Safety System Software is used for

device configuration. The following shows the

minimum software/firmware releases:

CHANNEL 8

CHANNEL 7

CHANNEL 6

CHANNEL 5

CHANNEL 4

CHANNEL 3

CHANNEL 2

CHANNEL 1

COM

6

5

4

3

2

1

COM 2 SHLD
COM 2 B
COM 2 A
COM 1 SHLD
COM 1 B
COM 1 A

SHLD

B
A

SHLD

B
A

LON FROM

PREVIOUS DEVICE

LON TO

NEXT DEVICE

POWER

6

5

4

3

2

1

SHLD

+
SHLD

+

SHLD

*


+

SHLD

*


+

24 VDC

INPUT VOLTAGE

24 VDC

INPUT VOLTAGE

EQ3720RM

TO

EARTH

GROUND

C2206

COMMON A

NO B

NC C

COMMON A

NO B

NC C

COMMON A

NO B

NC C

COMMON A

NO B

NC C

COMMON A

NO B

NC C

COMMON A

NO B

NC C

COMMON A

NO B

NC C

COMMON A

NO B

NC C

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

*

SHIELDS ON POWER WIRES ARE OPTIONAL

UNLESS REQUIRED BY LOCAL CODES.

NOTE: RELAY CONTACTS SHOWN IN REST (DE-ENERGIZED) STATE.

Figure 3-45— Relay Module Wiring Terminal Configuration