Startup – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 44

Advertising
background image

3-25

14.1

95-8533

6. Connect the “B” terminal on the power supply

monitor to the negative (–) side of the backup

battery. Connect a correctly sized circuit breaker in

the battery circuit as shown in Figure 3-21. The

circuit breaker must be rated between 130% and

250% of the total load.

7. Connect the “C” terminal on the power supply

monitor to the negative (–) side of the power supply.

8. Wire the power distribution circuit breakers to the output

of the power supply. Circuit breaker ratings must be

between 130% and 250% of the full load rating.

9. Set the device network address for the power

supply monitor.

NOTE

For additional information, refer to the power
supply manufacturer’s instruction manual
provided with the support documentation
received with the Eagle Quantum Premier
system.

STARTUP

Turn on the power supply and allow the voltage to

stabilize at 27 volts before closing the circuit to the

battery.

1

4

C

B

AC BREAKER

DC BREAKER

H

N

G

+

24 VDC

OUTPUT

POWER SUPPLY MONITOR

12

11
10

9
8

7
6

5
4
3

2

1

EQ21XXPS POWER SUPPLY

(See Note 9)

+

12 VDC

+

12 VDC

NRTL DISTRIBUTION CABINET

BATTERY

CIRCUIT

BREAKER

+

+

+

+

+

POWER DIST CKT #1

POWER DIST CKT #2

POWER DIST CKT #3

POWER DIST CKT #4

NOTES
1. AC INPUT SELECTABLE (THROUGH THE OIS) FOR 120 / 208 / 240 VAC.
2. BATTERY SIZE CALCULATED BASED ON SYSTEM LOAD.
3. CIRCUIT BREAKER SHALL PROTECT AGAINST EXCESSIVE CURRENT LOAD.
4. REMOVAL OF TERMINAL PLUG WITH POWER APPLIED TO TERMINALS B AND C

WILL DAMAGE POWER SUPPLY MONITOR.

5. NRTL DISTRIBUTION CABINET IS KEY LOCKED ENCLOSURE.
6. DASH LINES DENOTE PROTECTION AGAINST PHYSICAL DAMAGE.
7. ANY PRIMARY AND SECONDARY POWER SUPPLY UNITS MAY BE INSTALLED

EXTERNALLY TO THE NRTL DISTRIBUTION CABINET, PROVIDED THEY ARE

PROTECTED AGAINST PHYSICAL DAMAGE. ALL DEDICATED BRANCH CIRCUITS

AND CONNECTIONS BETWEEN PRIMARY AND SECONDARY POWER SUPPLY UNITS

AND THE NTRL DISTRIBUTION CABINET SHALL ALSO BE PROTECTED AGAINST

PHYSICAL DAMAGE.

8. SUPERVISION (SINGLE OPENS & GROUNDS) OF THE INTERCONNECTIONS

BETWEEN POWER SUPPLY (24 VDC OUTPUT) TO NRTL DISTRIBUTION CABINET

AND BACKUP BATTERIES TO NRTL DISTRIBUTION CABINET IS PERFORMED BY

EQ2100PSM POWER SUPPLY MONITOR.

9. THE CIRCUIT DISCONNECTING MEANS (AC & DC BREAKERS) SHALL BE

ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL.

10. AC WIRING CABLE MUST BE ≤20 FEET IN CONDUIT.

E1951

AC MONITOR

BACKUP BATTERIES

AC POWER

See Notes 1 & 3

See Note 3

See Note 2

See Note 4

See Note 10

See Note 6

TERMINAL J1

Figure 3-21— Wiring Connections for a Power Supply Monitor, EQ21XXPS Series Power Supply and Backup Batteries