14.1

3-12

95-8533

NOTE

The recommended lubricant is a silicone free
grease, available from Det-Tronics.

6. Set the node address for the device. (See “Setting

Device Network Addresses” in this section.)

7. Place the cover on the junction box and tighten

only until snug. DO NOT over tighten.

1

2

3

4

5

6

7

8

9

10

IDC

MANUAL PULL STATION

OR OTHER CONTACT DEVICE

14

13

12

11

+

+

24 VDC

+

+

A

B

A

B

CIRCUIT 1

CIRCUIT 2

COM 2

COM SHIELD

COM 1

EOL (10K)

EOL (10K)

A1871

Figure 3-5—Terminal Configuration for IDC

EQ22xxIDCGF SERIES INITIATING DEvICE
CIRCUIT GROUND FAULT
The following paragraphs describe how to properly

install and configure the EQ22xxIDCGF Initiating

Device Circuit Ground Fault.

Mounting
The device should be securely mounted to a vibration

free surface. (See “Specifications” in this manual for

device dimensions.)

Wiring

WARNING!

The enclosure must be electrically connected to
earth ground.

1. Remove the enclosure cover from the device.

2. Remove the communication module from the

junction box. Connect external wiring to the

appropriate points on the device terminal block.

(See Figure 3-4 for terminal block location and

Figure 3-6 for terminal identification)

3. Check wiring to ensure that ALL connections

have been properly made.

4. Inspect the enclosure O-ring to be sure that it is in

good condition. Lubricate the O-ring and the

threads of the enclosure cover to ease both

installation and future removal of the cover.

NOTE

The recommended lubricant is a silicone free
grease available from Detector Electronics.

Figure 3-6—Terminal Configuration for IDCGF

3

4

5

6

7

8

9

10

14

13

12

11

+

+

24 VDC

+

A

B

A

B

INPUT

COM 2

COM SHIELD

COM 1

68K OHM

RESISTOR

RELAY CONTACT

FOR MONITORING BATTERY.

CONTACT OPENS

WITH BATTERY TROUBLE CONDITION.

RELAY CONTACT

FOR MONITORING AC POWER.

CONTACT CLOSES

ON LOSS OF AC POWER.

B1922

NOTE: ENCLOSURE AND/OR MOUNTING BRACKET

MUST BE CONNECTED TO EARTH GROUND.