Fiber-Optic Cables

Disconnect Drive Control Pod Wiring Connections

Frame 8 drives, with drive control pod installed, complete steps 1 and 2 of this
procedure.

Frame 9 and larger drives, with drive control pod installed, complete steps 1
through 7 of this section.

If the drive control pod is mounted remotely, skip this section.

1.

Remove the right front cover.

IMPORTANT

Fiber-optic cables have a minimum bend radius of 50 mm (2 in.). If cables are over
bent, damage will occur.

IMPORTANT

For Frame 8 drives, the fiber-optic cables used to connect the fiber interface board to
both the converter (AC Input) / DC precharge (DC Input) control board and the inverter
power layer interface board must be the same length. The cables provided are 560 mm
(22 in.) in length.

IMPORTANT

For Frame 9 and larger drives, the fiber-optic cables used to connect the fiber interface
board to the power layer interface board must be the same length. The cables provided
are 2.8 m (110 in.) in length.

T20 or F 6.4 mm (0.25 in.)
1.8 N•m (16.0 lb•in)

Floor Mount Frame 8 Shown