Rockwell Automation Publication 750-IN001N-EN-P - April 2014

PowerFlex 750-Series AC Drives

Fuse and Circuit Breaker Ratings

The tables on the following pages provide recommended AC line input fuse and
circuit breaker information. See Fusing and Circuit Breakers on the next page for
UL and IEC requirements. Sizes listed are the recommended sizes based on 40 °C
(104 °F) and the U.S. NEC. Other country, state, or local codes can require
different ratings. DC link fuse recommendations for DC input drives are also
provided. In addition, Frame 8 and larger drives include AC line fuses (with
blown fuse indicators) to provide drive short circuit protection.

Input Device Requirements

Frames

Enclosure
Catalog Code

Enclosure Type

Installation Type

UL Certification Required

UL Certification
Not Required

1

R

IP20
NEMA/UL Open Type

Installed in a non-ventilated cabinet.

All devices listed on pages

154

and

158

are

acceptable.

All devices listed on pages

154

through

167

are

acceptable.

Installed outside of cabinet using NEMA
Type 1 kit or in a ventilated cabinet.

Only non-time delay fuses listed on pages

154

and

158

, excluding maximum value, are

acceptable.

2…5

N

IP20
NEMA/UL Open Type

Installed in a non-ventilated cabinet. Heat
sink is inside or outside of cabinet.

All devices listed on pages

154

,

158

,

162

, and

166

are acceptable.

F

Flange

N

IP20
NEMA/UL Open Type

Installed outside of cabinet using NEMA
Type 1 kit or in a ventilated cabinet.

400V AC/540V DC or 480V AC/650V DC drives:
Only non-time delay fuses listed on pages

154

and

158

, excluding maximum value, are

acceptable.
600V AC/810V DC drives:
Only non-time delay fuses listed on page

162

are acceptable, with maximum value of 40A
(Frame 3), 60A (Frame 4) and 100A (Frame 5).

F

Flange

G

IP54
NEMA/UL Type 12

Installed inside or outside of any cabinet.

All devices listed on pages

154

,

158

,

162

, and

166

are acceptable.

6…7

N

IP00
NEMA/UL Open Type

Installed in any cabinet.
Heat sink is inside or outside of cabinet.

400V AC/540V DC or 480V AC/650V DC drives:
All devices listed on pages

154

,

158

,

162

, and

166

are acceptable.

600V AC/810V DC or 690V AC/932V DC drives:
Only time delay and non-time delay fuses
listed on pages

162

and

166

are acceptable.

Installed outside of cabinet using NEMA
Type 1 kit.

G

IP54
NEMA/UL Type 12

Installed inside or outside of any cabinet.

All devices listed on pages

154

,

158

,

162

, and

166

are acceptable.

8…10

B, L, P, W

IP20
NEMA/UL Type 1

Installed inside of any cabinet.

All devices listed on pages

156

,

160

,

164

and

167

are acceptable.

J, K, Y

IP54
NEMA 12

Installed inside of any cabinet.

All devices listed on pages

156

,

160

,

164

and

167

are acceptable.