PowerFlex 750-Series AC Drives

Step 5: I/O Wiring

Important points to remember about I/O wiring:

Always use copper wire.

Wire with an insulation rating of 600V or greater is recommended.

Control and signal wires should be separated from power wires by at least
0.3 meters (1 foot).

For CE compliance, 115 volt digital input wiring must be shielded or must
not exceed 30 meters (98 feet) in length.

In order to maintain electrical safety for all user-accessible low voltage
circuits (SELV and PELV circuits), I/O terminals designated for 24V or
lower voltage must not be connected to a circuit of higher voltage or a
circuit which is not adequately insulated from dangerous voltages with
double or reinforced insulation within other connected equipment or
wiring.

In order to provide electrical safety for user-accessible low voltage I/O
circuits which are referenced to earth (PELV circuits) and which may be
touched simultaneously, care should be taken to provide a common earth
reference for all equipment connected to the drive.

IMPORTANT

I/O terminals labeled “(–)” or “Common” are not referenced to earth ground and are
designed to greatly reduce common mode interference. Grounding these terminals can
cause signal noise.

ATTENTION: Hazard of personal injury or equipment damage exists when using bipolar
input sources. Noise and drift in sensitive input circuits can cause unpredictable changes
in motor speed and direction. Use speed command parameters to help reduce input
source sensitivity.