Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual

Page 279

Advertising
background image

Rockwell Automation Publication 750-IN001N-EN-P - April 2014

279

PowerFlex 750-Series AC Drives

Control Wiring - Frame 9 and 10 Drives with Cabinet Options

Frame 9 drives are shipped from the factory with control power set to 120V AC. To change
control voltage to 230V AC, move the jumper as shown.

Table 101 - Control Power for Customer Use Voltage Selection - Floor Mount Frames 9 and 10 Drives

Control terminal block TB4 is mounted on the power option module. TB1 referenced in
the illustrations below resides on the main control board. See

page 213

.

Figure 143 - Control Terminal Blocks TB3 and TB4 - Floor Mount Frames 9 and 10 Drives

120V AC, 60Hz, 4.2A (Factory Setting)

230V AC, 50Hz, 2.2A

TB3(H)

T1 (X2)

FU12

600V AC, 3A, Class CC

TB3(H)

TB4(6)

FU12

600V AC, 6A, Class CC

Reactor Thermostat

Thermostat with Reactor - Frame 9 Only

TB4(2)

TB6(2)

TB6(3)

TB4(4)

TB6(4)

TB4(1)

TB4(3)

TB6(1)

TB1(Di 0dc)

TB1(+24V)

TS1

Thermostat without Reactor - Frames 9 and 10

TB6(2) TB4(2) TB6(3)

TB6(4)

TB4(1)

TB4(4)

TB6(1)

TB1(Di 0dc)

TB1(+24V)

TS1

TB3

TB4

Advertising
This manual is related to the following products: