Rockwell Automation Publication 750-IN001N-EN-P - April 2014

221

PowerFlex 750-Series AC Drives

120V Output Wiring for Drive Control

The Common DC Input drive provides limited 120V control power for use with
the drive control pod option modules. For terminal block wiring specifications
see

Table 34 - on page 204

.

Table 52 - TB5 Terminal Designations

Table 53 - TB5 Jumper Settings

Fixed I/O

Terminal

Name

Description

Rating

1

UPS 120VAC OUT HOT

Jumper combinations
select the source of the
120V AC output for drive
control. See

Table 53

.

120V AC, 50/60 Hz,
0.4 A, 48 VA
Fusing: 1A, 600V,
Class CC, Time Delay

2

120VAC HOT

3

CONTROL 120VAC OUT HOT

4

UPS 120VAC OUT NEUTRAL

5

120VAC NEUTRAL

6

CONTROL 120VAC OUT NEUTRAL

7

120VAC OUT NEUTRAL

Drive supplied 120V AC
output for drive control.

8

120VAC OUT HOT

120V AC from Control Transformer

Factory Jumper Settings:
TB5-2 and TB5-3
TB5-5 and TB5-6

120V AC from User Supplied UPS

User Jumper Settings:
TB5-1 and TB5-2
TB5-4 and TB5-5

ATTENTION: Hazard of personal injury or equipment damage exists if jumpers are
incorrectly set. Verify jumpers are set for control scheme used before energizing the
circuit.

1

2

3

4

5

6

7

8

2

3

5

6

1

2

3

4

5

6

1

2

3

4

5

6

7

8

120V AC Output Neutral

Hot

120V AC Input Neutral

Hot

1 A

N 120 240 T1

1KVA

SW2

8

7

TB5

TB2

1

2

4

5

1

2

3

4

5

6

1

2

3

4

5

6

7

8

120V AC Output Neutral

Hot

120V AC UPS Input Neutral

Hot

1 A

SW2

TB5

TB2

6

Advertising