Safety Enable Circuitry

The drive ships with the safety enable jumper (SAFETY) installed. This jumper
must be removed when using the safe torque off or speed monitoring safety
options.

PowerFlex 753 - SAFETY Jumper Location

PowerFlex 755 - SAFETY Jumper Location (Wall Mount Frames 1…7 Only)

Note:

Floor Mount Frame 8 drives and larger do not have a safety enable jumper.

IMPORTANT

Failure to remove the jumper when using either safety option will cause the drive to
fault when a start command is issued.