Dual incremental encoder option module – Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual

Page 258

Advertising
background image

258

Rockwell Automation Publication 750-IN001N-EN-P - April 2014

PowerFlex 750-Series AC Drives

Dual Incremental Encoder Option Module

Table 88 - Dual Incremental Encoder Jumper Settings

Table 89 - Dual Incremental Encoder Specifications

20-750-DENC-1

20-750-S1

20-750-DENC-1

See Important statement on this page.

Jumper

Enabled Position

Storage Position

P3 - Safety Jumper
Enables use with speed
monitoring safety option
(20-750-S1).

P4 - 12V Jumper
Enables use with 12 volt
supply in “Enabled”
position and 5 volt supply
in “Storage” position.

Consideration

Description

Input

Differential or Single Ended operation, Constant Current Sink operation ~10 mA

5V DC minimum to 15V DC maximum sourcing 10 mA
minimum high state voltage of 3.5V DC
maximum low state voltage of 0.4V DC

Maximum Cable Length

30 m (100 ft) @ 5V, 183 m (600 ft) @ 12V

Maximum Input Frequency

250 kHz

IMPORTANT

When used with the Safe Speed Monitor option, both modules must be installed on
the same backplane using ports 4, 5, or 6.

P3

P3

P4

P4