Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual

Page 223

Advertising
background image

Rockwell Automation Publication 750-IN001N-EN-P - April 2014

223

PowerFlex 750-Series AC Drives

Uninterruptible Power Supply Connections - Common DC Input Drives

The user-supplied 120V AC UPS is connected to the lower 120V rail in the back
of the Common DC Input drive cabinet. The UPS rail is only installed when the
P30 UPS Control Bus option is selected. The rail is connected to TB2-1 and
TB2-2 on the Common DC Input drive control panel. To use 120V AC UPS
power, configure the TB5 jumpers as shown in

Table 53 - on page 221

.

Figure 113 - UPS Connection Terminals - Floor Mount Frames 8…10

ATTENTION: To avoid an electric shock hazard when servicing the drive, a means for
Lockout/Tagout of an external 120V uninterruptible power supply must be provided. Or
the circuit breaker SW5 must be locked and tagged. Locking and tagging the common
bus precharge disconnect switch SW2 alone does not provide sufficient protection
when servicing the drive.

29.0

(1.1)

11.0

(0.4)

63.0

(2.5)

1/4-20

4X

7/16 in.
5.1 N•m (45.0 lb•in)

Hot

Neutral

IMPORTANT

The UPS wiring is internally wired through the DC input drive disconnect switch SW2
ahead of the UPS terminal connections.