Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual

Page 173

Advertising
background image

Rockwell Automation Publication 750-IN001N-EN-P - April 2014

173

PowerFlex 750-Series AC Drives

21G…D800

LD

800

100

ND

700

100

HD

600

100

21G…D960

LD

900

100

ND

800

100

HD

700

100

21G…D1K0

LD

1000

100

ND

900

100

HD

750

100

21G…D1K2

LD

1100

100

ND

1000

100

HD

800

100

21G…D1K3

LD

1250

100

ND

1100

100

HD

900

100

21G…D1K4

LD

1350

100

ND

1250

100

HD

1000

100

(1) These circuit breakers are considered Branch Circuit Protection for the unit.
(2) No additional protection is provided with the P5 Molded Case Switch option. Branch circuit protection is required based on NEC guidelines.

Drive Catalog
Number

Duty
Cycle

Hp

Short Circuit Current Rating (kA)

Circuit Breaker
Only (P3)

(1)

Circuit Breaker with Input Contactor
(P3 with P11)

(1)

Molded Case Switch Only
(P5)

(2)

Molded Case Switch with Input Contactor
(P5 with P11)

(2)

480 Volt AC Input

Advertising