Floor Mount Frames 8…10 Power Terminal L-Brackets

Frame 8 drives and larger utilize movable L-bracket assemblies to connect AC
line input power, output to motor, and DC power to the extruded bus bars at the
back of the cabinet. Wiring must be connected to the L-brackets using customer-
supplied lugs (either crimp or mechanical type) and customer-supplied hardware.
See

Figure 88

.

Additional Power Terminal L-Brackets

Frame 8 and larger drives come equipped with two L-brackets per AC phase. If an
application requires additional L-brackets, kit number 20-750-LBRKT1 is
available. Each kit contains three L-brackets and mounting hardware.

Figure 87 - L-Bracket Approximate Dimensions

Crimp terminals should be applied to cabling using the vendor-recommended
tooling. Mechanical terminals should be torqued per vendor instructions. When
using mechanical terminals, which may be large, be sure to maintain adequate
spacing to adjacent wires, terminals, and other parts.

IMPORTANT

Verify that clamp fits squarely in the bus bar
channel

M10 x 1.5

38.0 N•m (336 lb•in)

17 mm

52.7

(2.25)

85.1

(3.35)

ш 14.0

(0.55)

21.2

(0.83)

44.5

(1.75)