Rockwell Automation Publication 750-IN001N-EN-P - April 2014

PowerFlex 750-Series AC Drives

Analog Current Input
Unipolar Speed Reference
0-20 mA Input

22-Series I/O Module TB1

Set Direction Mode

Port 0: P308 [Direction Mode] = 0 “Unipolar”

Set Selection

Port 0: P545 [Spd Ref A Sel] = Port X (22-Series I/O Module): P50 [Anlg In0 Value]

Adjust Scaling

Port X (22-Series I/O Module): P51 [Anlg In0 Hi] = 20 mA
Port X (22-Series I/O Module): P52 [Anlg In0 Lo] = 0 mA
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz

View Results

Port X (22-Series I/O Module): P50 [Anlg In0 Value]
Port 0: P592 [Selected Spd Ref]

HW Input PTC
Standard = DIN 44082
PTC Nominal = 1.8 k Ohm
PTC Trip = 3.1 k Ohm
PTC Reset = 2.2 k Ohm
Short Circuit Trip = 300 Ohm

22-Series I/O Module TB1

Configuration

Port X (22-Series I/O Module): P40 [PTC Cfg] = 0 “Ignore,” 1 “Alarm,” 2 “Flt Minor,”
3 “Flt CoastStop,” 4 “Flt RampStop,” or 5 “Flt CL Stop”

View Results

Port X (22-Series I/O Module): P41 [PTC Sts]
Port X (22-Series I/O Module): P42 [PTC Raw Value]

Analog Voltage Output
±10V, 0…20 mA Bipolar
+10V Unipolar

22-Series I/O Module TB1

Configuration

Port X (22-Series I/O Module): P70 [Anlg Out Type], bit 0 = 0

Set Selection

Port X (22-Series I/O Module): P75 [Anlg Out0 Sel] = Port 0: P3 [Mtr Vel Fdbk]

Adjust Scaling

Port X (22-Series I/O Module): P78 [Anlg Out0 DataHi] = 60 Hz
Port X (22-Series I/O Module): P79 [Anlg Out0 DataLo] = 0 Hz
Port X (22-Series I/O Module): P80 [Anlg Out0 Hi] =10V/20 mA
Port X (22-Series I/O Module): P81 [Anlg Out0 Lo] = 0V/0 mA

View Results

Port X (22-Series I/O Module): P77 [Anlg Out0 Data]
Port X (22-Series I/O Module): P82 [Anlg Out0 Val]

2-Wire Control Non-
Reversing
24V DC internal supply

22-Series I/O Module TB1

Set Direction Mode

Port 0: P308 [Direction Mode] = 2 “Rev Disable”

Configuration

Port 0: P150 [Digital In Cfg] = 1 “Run Level”

Set Selection

Port 0: P163 [DI Run] = Port X (22-Series I/O Module): P1 [Dig In Sts], bit 0 = Input 0

View Results

Port X (22-Series I/O Module): P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]

2-Wire Control Reversing
External 24 volt supply

20-750-2262C-2R
20-750-2263C-1R2T

22-Series I/O Module TB1

Set Direction Mode

Port 0: P308 [Direction Mode] = 0 “Unipolar”

Configuration

Port 0: P150 [Digital In Cfg] = 1 “Run Level”

Set Selection

Port 0: P164 [DI Run Forward] = Port X (22-Series I/O Module): P1 [Dig In Sts], bit 0 = Input 0
Port 0: P165 [DI Run Reverse] = Port X (22-Series I/O Module): P1 [Dig In Sts], bit 1 = Input 1

View Results

Port X (22-Series I/O Module): P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]

22-Series I/O Module TB1 Wiring Examples (Continued)

Input/Output

Connection Example

Required Parameter Changes

Ai0–

Ai0+

Common

+

Ai0

Ai1

1.8k

PTC

Ptc–

Ptc+

ATTENTION: To avoid an electric shock hazard, the connection of the motor
temperature sensor requires double or reinforced insulation between motor live parts
and the PTC.

Ao0–

Ao0+

+

24VC

+24V

Di C

Di 0

Stop-Run

Di C

Di 0

Di 1

+24V

Common

Run Fwd

Run Rev