Series i/o with atex module – Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual

Page 231

Advertising
background image

Rockwell Automation Publication 750-IN001N-EN-P - April 2014

231

PowerFlex 750-Series AC Drives

Table 56 - TB2 Terminal Designations (2 Relay Outputs: 2R)

Table 57 - TB2 Terminal Designations (1 Relay and 2 Transistor Outputs: 1R2T)

Table 58 - 24 Volt DC Power Supply Source for Digital Inputs Jumpers

11-Series I/O with ATEX Module

The 11-Series I/O option module can be used with the ATEX option module,
catalog number 20-750-ATEX. For detailed information on installation of 11-
Series I/O with the ATEX option module, refer to the PowerFlex 750-Series
ATEX User Manual, publication

750-UM003

.

Relay Out

Terminal

Name

Description

Related
Param

R0NO

Relay 0 N.O.

Relay Normally Open contact output:
240V AC, 30V DC, 3.5 A max.
General Purpose (Inductive) / Resistive

Relay Normally Closed contact output:
240V AC, 30V DC, 5 A max.
Resistive Only

10, 100,
101, 105,
106
on Port X

R0C

Relay 0 Common

R0NC

Relay 0 N.C.

R1NO

Relay 1 N.O.

20, 110,
111, 115,
116
on Port X

R1C

Relay 1 Common

R1NC

Relay 1 N.C.

Relay Out

Terminal

Name

Description

Related
Param

R0NO

Relay 0 N.O.

Relay Normally Open contact output:
240V AC, 24V DC, 3.5 A max.
General Purpose (Inductive) / Resistive

Relay Normally Closed contact output:
240V AC, 24V DC, 5 A max.
Resistive Only

10, 100,
101, 105,
106
on Port X

R0C

Relay 0 Common

R0NC

Relay 0 N.C.

T0

Transistor Output 0

Transistor output
Rating:

24V DC = 1 A max. including U.L.
applications
Resistive

20
on Port X

TC

Transistor Output
Common

T1

Transistor Output 1

30
on Port X

Internal

External

Important: 24 Volt DC supply is only used with modules 20-750-1132C-2R and 20-750-1133C-1R2T.

R0NO

R0C

R0NC

R1NO

R1C

R1NC

R0NO

R0C

R0NC

T0

TC

T1

P3

P8

3

1

3

1

P3

P8

3

1

3

1