Series i/o module – Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual

Page 230

Advertising
background image

230

Rockwell Automation Publication 750-IN001N-EN-P - April 2014

PowerFlex 750-Series AC Drives

11-Series I/O Module

Table 54 - Analog Input Mode Jumpers

Table 55 - TB1 Terminal Designations

20-750-1132C-2R (24 Volts DC)

20-750-1133C-1R2T (24 Volts DC)

20-750-1132D-2R (120 Volts AC)

Voltage Mode

Current Mode

Terminal

Name

Description

Related
Param

(4)

(4) I/O Module parameters will also have a Port designation.

–10V

–10 Volt Reference

Negative 10V DC for analog inputs. 2k ohm minimum.

10VC

10 Volt Common

For (–) and (+) 10 Volt references.

+10V

+10 Volt Reference

Positive 10V DC for analog inputs. 2k ohm minimum.

Sh

Shield

Terminating point for wire shields when an EMC plate
or conduit box is not installed.

Ao0–

Analog Out 0 (–)

Bipolar, ±10V, 11 bit & sign, 2 k ohm minimum load.
4-20 mA, 11 bit & sign, 400 ohm maximum load.

75
on Port X

Ao0+

Analog Out 0 (+)

Sh

Shield

Terminating point for wire shields when an EMC plate
or conduit box is not installed.

Ai0–

Analog Input 0 (–)

Differential

(2)

, bipolar, 11 bit & sign.

Voltage Mode: ±10V @ 88k ohm input impedance.
Current Mode: 0-20 mA @ 93 ohm input impedance.

(2) Differential - External source must be maintained at less than 160V with respect to PE. Input provides high common mode

immunity.

50, 70
on Port X

Ai0+

Analog Input 0 (+)

Sh

Shield

Terminating point for wire shields when an EMC plate
or conduit box is not installed.

Di0

Digital Input 0

24V DC (30V DC Max.) - Opto isolated
High State: 20…24V DC 11.2 mA DC
Low State: 0…5V DC
120V AC (132V AC Max.) 50/60 Hz

(3)

- Opto isolated

High State: 100…132V AC
Low State: 0…30V AC

(3) For CE compliance use shielded cable. Cable length should not exceed 30 m (98 ft).

1
on Port X

Di0P

Digital Input 0 Power

(1)

(1) Digital Inputs are either 24 Volts DC (1132C) or 115 Volts AC (1132D) based on module catalog number. Ensure applied voltage is

correct for I/O module.

Di1

Digital Input 1

Di1P

Digital Input 1Power

(1)

Di2

Digital Input 2

Di2P

Digital Input 2 Power

(1)

Ip

Input Power

External 24V DC or 115V AC power supply input
connections.

Ic

Input Common

EnC

Enable Output

ATEX fault enable output. Used only when an ATEX
option module is installed.

EnNO

ATTENTION: Risk of equipment damage exists. Ensure that the correct voltage is
applied to the I/O Module digital inputs. Refer to the I/O Module catalog number to
determine the voltage rating.

20-750-1132C-2R is rated 24 Volts DC

20-750-1133C-1R2T is rated 24 Volts DC

20-750-1132D-2R is rated 120 Volts AC

P5

1

2

P4

1

2

P5

1

2

P4

1

2

–10V
10VC
+10V
Sh
Ao0–
Ao0+
Sh
Ai0–
Ai0+
Sh
Di0
Di0P
Di1
Di1P
Di2
Di2P
Ip
Ic
EnC
EnNO